6. Protection Control
6.1
High Pressure Protection Control
This high pressure protection control is used to prevent the activation of protection devices due to
abnormal increase of high pressure and to protect compressors against the transient increase of
high pressure.
Cooling
Normal Operation
21-step down
9-step up
9-step down
3-step up
2-step down
1-step up
2-step down
After 10 seconds
After 15 seconds
After 15 seconds
After 10 seconds
Pc > 3.57 MPa
(518 psi)
Pc > 3.70 MPa
(537 psi)
Pc < 3.14 MPa
(455 psi)
Pc < 3.45 MPa
(500 psi)
Pc > 3.67 MPa
(532 psi)
Pc > 3.62 MPa
(525 psi)
Pc > 3.57 MPa
(518 psi)
Compressor step: 1
After 15 seconds
Pc < 3.33 MPa (483 psi)
After 10 seconds
Upper limit compressor step: max (Max. Step)
Pc > 3.72 MPa
(540 psi)
Pc: High pressure sensor
detection value for each
outdoor unit
Current
step
maintained
Abnormal stop
(
E3
is displayed)
High pressure standby
(2 times within 40 minutes)
After 10
seconds
High pressure switch (4.0 MPa
(580 psi)) is activated
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...