Troubleshooting by Error Code
Service Diagnosis
224
2.38 Harness Abnormality (between Outdoor Unit Main PCB
and Inverter PCB)
Error Code
H3
Applicable
Models
All outdoor unit models
Method of Error
Detection
Check for the transmission conditions of the harnesses between the PCBs using microcomputer.
Error Decision
Conditions
Normal transmission between the PCBs is disabled while the compressor stops running.
Supposed
Causes
Defective connection of jumpers between PCB
Defective outdoor unit main PCB (A1P)
Defective inverter PCB
Troubleshooting
Check for the transmission
conditions of the following
harnesses.
(1) X6A (Inverter PCB)
↔
X28A (A1P)
(2) X63A (Inverter PCB)
↔
X40A (A1P)
Replace the outdoor unit main
PCB (A1P).
Replace the inverter PCB.
RXLQ-TATJU,
RXLQ-TAYDU: A3P
RXLQ-TAYCU,
RXYQ-TAYCU: A4P
YES
NO
YES
Complete countermeasures.
Return the relevant harness to
normal.
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Harness error
H3
error recurs.
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...