Troubleshooting by Error Code
SiUS341802E
223
Service Diagnosis
2.37 Refrigerant Overcharged
Error Code
F6
Applicable
Models
All outdoor unit models
Method of Error
Detection
Detect overcharged refrigerant according to outdoor air temperature, heat exchanger deicer
temperature, and liquid pipe temperature during check operation.
Error Decision
Conditions
When the amount of refrigerant, which is calculated using outdoor air temperature, heat exchanger
deicer temperature, and liquid pipe temperature during check operation, exceeds the regular
charge amount by 30% or more
(If refrigerant is charged slightly over the regular charge amount,
F6
may be displayed on the
remote controller.)
Supposed
Causes
Refrigerant overcharged
Disconnection of outdoor air thermistor
Disconnection of heat exchanger deicer thermistor
Disconnection of liquid pipe temperature thermistor
Troubleshooting
Check for the conditions of
mounting of the temperature
sensors of the outdoor air
thermistor, the heat exchanger
thermistor, and liquid pipe
thermistor to the piping.
Disconnect the outdoor air
thermistor, the heat exchanger
thermistor, and liquid pipe
thermistor from the outdoor
unit PCB, and then make
measurement of resistance
using a multimeter.
Normal?
Remedy refrigerant overcharging.
YES
NO
NO
Replace the abnormal thermistors,
and then operate the system.
Properly connect the thermistors,
and then operate the system.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
CHECK 11
Are the temperature
sensors properly
mounted?
CHECK 11
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...