Field Settings from Remote Controller
SiUS341802E
109
Field Settings and Test Operation
FXSQ-TA model
The Second Code No. is set to
05
(an external static pressure of 50 Pa (0.20 inWG)) at factory setting.
∗
1. FXSQ18-48TA cannot be set to 30-40 Pa (0.12-0.16 inWG).
∗
2. FXSQ54TA cannot be set to 30-40 Pa (0.12-0.16 inWG) or 150 Pa (0.60 inWG).
Optional Kit Setting (UV lamp + Humi Economizer) (for FXTQ-TA model)
Residential Dry (for FXTQ-TA model)
Drain Pump Operation Settings (for FXMQ-PB model)
The drain pump operation can be disabled for natural drainage by changing the following field setting.
Mode No.
First Code No.
Second Code No.
Contents
13 (23)
6
03
30 Pa (0.12 inWG) (
∗
1) (
∗
2)
04
40 Pa (0.16 inWG) (
∗
1) (
∗
2)
05
50 Pa (0.20 inWG)
06
60 Pa (0.24 inWG)
07
70 Pa (0.28 inWG)
08
80 Pa (0.32 inWG)
09
90 Pa (0.36 inWG)
10
100 Pa (0.40 inWG)
11
110 Pa (0.44 inWG)
12
120 Pa (0.48 inWG)
13
130 Pa (0.52 inWG)
14
140 Pa (0.56 inWG)
15
150 Pa (0.60 inWG) (
∗
2)
Mode No.
First Code No.
Second Code No.
Contents
UV lamp + humidifier fan
speed
Economizer setting for
Mech standby duration
(minutes)
14 (24)
4
01
Refer to controller
10
02
High
10
03
Refer to controller
20
04
High
20
05
Refer to controller
30
06
High
30
07
Refer to controller
40
08
High
40
09
Refer to controller
50
10
High
50
11
Refer to controller
60
12
High
60
13
Refer to controller
Free cooling only
14
High
Free cooling only
Mode No.
First Code No.
Second Code No.
Contents
14 (24)
5
01
Set temperature: room temperature
02
Set temperature: same as cooling set temperature
Mode No.
First Code No.
Second Code No.
Contents
15 (25)
0
01
—
02
ON
03
OFF
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...