SiUS341802E
Troubleshooting by Error Code
Service Diagnosis
168
2.1.2 External Protection Device Abnormality (FXTQ-TA Only)
Error Code
A0-01
Applicable
Models
FXTQ-TA
Method of Error
Detection
Detect open or short circuit between external input terminals in indoor unit.
Error Decision
Conditions
When an open circuit occurs between external input terminals.
Supposed
Causes
Actuation of external protection device
Defective indoor unit PCB
Indoor unit fuse blown
Troubleshooting
Fuse (F1U)
is blown.
Ex
ternal
protection device
is connected to TB4 and
TB5 of the indoor unit
terminal.
The
external protection
device is opened.
Replace the indoor unit PCB.
Actuation of external protection
device.
Replace the fuse (F1U).
YES
YES
NO
NO
NO
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...