SiUS341802E
Troubleshooting by Error Code
Service Diagnosis
200
Troubleshooting
Note:
∗
1. Connector
Diagnosis procedure 1
Infrared presence sensor
error (Error code
CE-01
)
Turn off the power and then reconnect.
Check infrared presence sensor output; refer to
sensor and address data No. 22-25.
Connect the connector correctly.
Connect the connector correctly.
NO
YES
YES
Is the
connection
of the connector
on infrared presence
sensor PCB (A4P) and the
connector (
∗
1) on
A2P normal?
NO
YES
YES
Is the
connection of the
sensor connector
normal?
Normal.
NO
Displays
15
by the above
verification method.
Normal.
NO
Displays
CE-01
again or
15
for
sensor and
address data.
Replace the sensor.
Model
Connector for infrared presence sensor PCB
FXFQ-T
X2A
FXUQ-P
X81A
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...