Special Control
SiUS341802E
61
Functions and Control
7.2
Oil Return Operation
In order to prevent the compressor from running out of oil, the oil return operation is conducted to recover oil that has
flowed out from the compressor to the system side.
Tc : High pressure equivalent saturation temperature
Te : Low pressure equivalent saturation temperature
TsA: Suction pipe temperature detected by thermistor R3T
7.2.1 Oil Return Operation in Cooling Operation
Starting conditions
Referring to the set conditions for the following items, start the oil return operation in cooling
• Cumulative oil feed rate
• Timer setting (Make this setting so as to start the oil return operation when the initial cumulative operating time reaches 2
hours after power supply is turned ON and then every 8 hours.)
Furthermore, the cumulative oil feed rate is computed from Tc, Te, and compressor loads.
Part Name
Electric Symbol
Oil return operation
Inverter compressor
M1C
Constant low pressure control
Inverter fan
M1F, M2F
For heat exchanger mode
Electronic expansion valve (Heat exchanger
upper)
Y1E
Same as normal operation
Electronic expansion valve (Heat exchanger
lower)
Y3E
Electronic expansion valve (Subcooling
heat exchanger)
Y2E
0 pulse
Electric expansion valve (Subcooling
injection)
Y4E
760 pulse
Electronic expansion valve (Refrigerant
cooling)
Y5E
Same as normal operation
Electronic expansion valve (Receiver gas
purge)
Y7E
0 pulse
Solenoid valve (Oil separator oil return)
Y1S
ON
Solenoid valve (Hot gas bypass)
Y2S
Same as normal operation
Solenoid valve (Liquid shutoff)
Y3S
ON
Four way valve (HP/LP gas pipe)
Y4S
Hold
Four way valve (Heat exchanger lower)
Y5S
Hold
Four way valve (Heat exchanger upper)
Y6S
Hold
Solenoid valve (Accumulator oil return)
Y7S
Same as normal operation
Ending condition
•
A lapse of 3 minutes
•
TsA – Te < 3
°
C (5.4°F)
•
A lapse of 12 minutes while the frequency is
more than that of oil return operation.
&
OR
Indoor unit actuator
Oil return operation
Fan
Thermostat ON unit
Remote controller setting
Stopping unit
OFF
Thermostat OFF unit
Remote controller setting
Electronic expansion valve
Thermostat ON unit
Normal control
Stopping unit
224 pulse
Thermostat OFF unit
Forced thermostat ON (PI control)
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...