Troubleshooting by Error Code
SiUS341802E
199
Service Diagnosis
2.24 Infrared Presence/Floor Sensor Error
Error Code
CE
Applicable
Models
FXFQ-T, FXUQ-P
Method of Error
Detection
The contents of a failure vary with the detailed error code. Check the code and proceed with the
flowchart.
Error Decision
Conditions
Error is detected based on sensor output signals
Supposed
Causes
Defective or disconnected infrared presence sensor connector:
CE-01
Defective infrared floor sensor (Temperature compensation circuit disconnection):
CE-02
Defective infrared floor sensor (Temperature compensation short circuit):
CE-03
Defective infrared floor sensor element:
CE-04
Troubleshooting
See diagnosis procedure 1.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Error code
CE-01
See diagnosis procedure 2.
Error code
CE-02
See diagnosis procedure 3.
Error code
CE-03
See diagnosis procedure 4.
Error code
CE-04
Error type varies according
to error code. Check the
error code and take the
following steps.
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...