Outline of Control (Indoor Unit)
SiUS341802E
89
Functions and Control
9.14 Fan Control (Heater Residual) (FXTQ-TA Models)
Outline
If the indoor heater turned OFF from ON during heating operation, the fan will keep operating for
further period of time in order to cool the heater.
Detail
∗
1. When the heater is ON, the airflow rate of the fan will be whichever is the largest between the
CFM dictated by the heater's own capacity, or the fan tap CFM determined by other controls.
∗
2. Fan residual operation will continue, even if the indoor unit is turned off with the remote
controller operation button.
9.15 Interlocked with External Equipment (FXTQ-TA Models)
9.15.1 Air Purifier (UV lamp)
When an air purifier is connected onsite, the fan is operated with the airflow rate set of the remote
controller or with the H tap.
∗
1. External input ON is an input signal to the X1M-AIR CLEANER terminal on the PCB.
∗
2. Field setting 14(24)-4. Refer to page 109.
9.15.2 Humidifier
When a humidifier is connected onsite, the fan operates with the airflow rate set of the remote
controller or with the H tap.
∗
1. External input ON is an input signal to the X1M-HUMIDIFIER terminal on the PCB.
∗
2. Field setting 14(24)-4. Refer to page 109.
Note:
This control is not applicable to the humidifier connected to the wiring adaptor, but to the humidifier
connected to HUMIDIFIER on the X1M terminal of the indoor unit PCB.
•
Heater turned OFF from ON
OR
•
Heater ON
•
Time up (
∗
2)
Residual OFF
Residual ON
Fan (
∗
1)
ENTRY/
90 sec. timer starts.
&
Fan X tap operation
(X tap is selectable by field setting. (
∗
2))
•
Remote control operation
(including thermostat OFF)
•
External input: ON (
∗
1)
&
&
•
Remote control operation: ON
(including thermostat OFF)
•
When the external input
changes from ON to OFF.
•
Remote control operation: ON
(including thermostat OFF)
•
External input: ON (
∗
1)
Fan X tap operation
(X tap is selectable by field setting. (
∗
2))
Fan residual operation for 30 seconds
(The fan airflow rate is set with the X tap.)
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...