Protection Control
SiUS341802E
57
Functions and Control
6.3
Discharge Pipe Protection Control
This discharge pipe protection control is used to protect the compressor internal temperature
against an error or transient increase of discharge pipe temperature.
Normal Operation
3-step down
9-step up
9-step down
3-step up
21-step down
After 30 seconds
After 20 seconds
After 20 seconds
After 30 seconds
A
(˚C) >
X
(˚C)
(
A
(˚F) >
Y
(˚F))
A
(˚C) <
X
–10
(˚C)
(
A
(˚F) <
Y
–18
(˚F))
A
(˚C) >
X
+5
(˚C)
(
A
(˚F) >
Y
+9
(˚F))
A
(˚C) <
X
–5
(˚C)
(
A
(˚F) <
Y
–9
(˚F))
A
(˚C) >
X
+10
(˚C)
(
A
(˚F) >
Y
+18
(˚F))
A
(˚C) >
X
+15
(˚C)
(
A
(˚F) >
Y
+27
(˚F))
A
(˚C) >
X
(˚C)
(
A
(˚F) >
Y
(˚F))
Compressor step: 1
After 20 seconds
HTdi > 135˚C (275˚F)
HTdi > 120˚C (248˚F)
continues for 10 minutes
Ti > 120˚C (248˚F)
continues for 5 seconds
Ti > 115˚C (239˚F)
continues for 10 minutes
OR
HTdi
: Value of inverter compressor discharge pipe temperature (Tdi) compensated with outdoor air temperature
Ti
: Compressor body temperature
A
: Maximum of HTdi and Ti
X(˚C)(Y(˚F)):
RXLQ72TA, RXYQ72-120TA
→
115˚C (239˚F) (constant)
RXLQ96/120TA, RXYQ144/168TA
→
Temperature determined by compressor rotation speed
Upper limit compressor step:
max (Max. Step)
Current
step
maintained
Discharge pipe temperature standby
(3 times within 100 minutes)
Abnormal stop
(
F3
is displayed)
Discharge pipe temperature
standby
(2 times within 100 minutes)
After 30
seconds
100
105
110
X (˚C)
212
221
230
80 90
120
Y (˚F)
Compressor
rotation speed (rps)
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...