Outline of Control (Indoor Unit)
SiUS341802E
79
Functions and Control
9.7
Freeze-up Prevention
Freeze-up Prevention by Off Cycle (Indoor Unit)
When the temperature detected by the liquid pipe temperature thermistor of the indoor heat exchanger drops too
low, the unit enters freeze-up prevention control in accordance with the following conditions, and is also set in
accordance with the conditions given below. (Thermostat OFF)
When freeze-up prevention is activated, the electronic expansion valve is closed, the drain pump turns on and
the airflow rate is fixed to L tap. When the following conditions for cancelling are satisfied, it will reset.
Conditions for starting:
Liquid pipe temperature
≤
– 1°C (30.2°F) (for total of 40 minutes)
or
Liquid pipe temperature
≤
– 5°C (23°F) (for total of 10 minutes)
Condition for cancelling:
Liquid pipe temperature
≥
+7°C (44.6°F) (for 10 minutes continuously)
The idea of freeze-up prevention control
Difficult to carry out freeze-up prevention operation
· For comfort, suppression of frequent thermostat ON/OFF is necessary.
· Suppressing the switching frequency of the compressor is required to ensure reliability.
After freeze-up prevention operation is carried out, the compressor can be defrosted properly.
· Water leakage prevention must be effective.
Normal operation
Start
Cancel
Liquid pipe
temperature
Start
Cancel
Normal operation
–
5
ºC
(23˚F)
0
ºC
(32˚F)
+
7
ºC
(44.6˚F)
–
1
ºC
(30.2˚F)
t1
t2
t3
t4
0
ºC
(32˚F)
+
7
ºC
(44.6˚F)
10 min.
OR
10 min.
10 min.
t
>
40
minutes
Freeze-up prevention control
Forced OFF by thermostat
Freeze-up prevention control
Forced OFF by thermostat
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...