SiUS341802E
Field Setting from Outdoor Unit
Field Settings and Test Operation
132
[2-38]: Emergency operation “Master”
To disable permanent compressor operation: in case of single module or “Master” unit of a multi outdoor
system, this setting allows:
Default value: 0. Compressor operation enabled.
Field setting:
Set 1 or 3: compressor in this “Master” module is disabled permanent.
[2-39]: Emergency operation “Slave 1”
To disable permanent compressor operation of “Slave 1” unit of a multi outdoor system (RXYQ-TA):
Default value: 0. Compressor operation enabled.
Field setting:
Set 1 or 3: compressor in this “Slave 1” module is disabled permanent.
[2-40]: Emergency operation “Slave 2”
To disable permanent compressor operation of “Slave 2” unit of a multi outdoor system (RXYQ-TA):
Default value: 0. Compressor operation enabled.
Field setting:
Set 1 or 3: compressor in this “Slave 2” module is disabled permanent.
Combination table setting 2-38, 2-39 and 2-40:
[2-42]: Outdoor fan noise countermeasure
Change fans rotational speed and reduce noise by the interference of air blow noise between outdoor
units.
Default value: 0
Field setting:
Mode A: 1
Mode B: 2
[2-49]: Height difference setting
Default value: 0.
In case the outdoor unit is installed in the highest position (indoor units are installed on a lower position
than outdoor units) and the height difference between the lowest indoor unit and the outdoor unit
exceeds 50 m(164 ft), the setting [2-49] has to be changed to 1.
[2-51]: Master/Slave setting Multi
When 2 or 3 modules are installed as a multi-outdoor (by common refrigerant piping and wiring by
terminals Q1Q2) configuration is automatically detected. In certain cases, the sequence of the slave
units need to be set manually (in case of AIRNET monitoring).
Default value: 0. Automatic detection.
Field setting: ensure that the modules in a multi are set different status. Even some modules in a multi
are set manually to same status, U7 error will appear.
1: forced “Master” (F1F2/Ind terminals should be connected to indoor units).
2: forced “Slave 1” (only Q1Q2 terminals should be wired to “Master” module).
3: forced “Slave 2” (only Q1Q2 terminals should be wired to “Master” module).
Disable
Master/individual
Slave 1
Slave 2
Module
2-38-1 or 2-38-3
2-39-1 or 2-39-3
2-40-1 or 2-40-3
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...