SiUS341802E
Troubleshooting by Error Code
Service Diagnosis
248
Troubleshooting
Note:
∗
1. Make measurement of voltage at the power supply terminal block (X1M).
∗
2. Make measurement of voltage at the L1, L2 and L3 terminals of diode module located on the
inverter PCB during the compressor is in operation.
Is supply
voltage imbalance
over approximately
12 V? (
∗
1)
Correct the open phase of
power supply.
Open phase?
Is the
imbalance of voltage
applied to the inverter over
approximately
12 V? (
∗
2)
Rectify the power supply
voltage imbalance.
Take countermeasures (listed
below).
YES
YES
NO
NO
NO
Take countermeasures.
Defective noise filter, magnetic
relay, or wiring
Turn OFF the power supply,
and then check and repair
wirings in the main circuit and
defective components.
(1) Loose contact and wiring
disconnection between the
power supply and the
inverter
(2) Adhesion, meltdown, or
loose contact of magnetic
relay
(3) Wiring disconnection in or
loose contact of noise filter
Replace the inverter PCB.
RXLQ-TATJU,
RXLQ-TAYDU: A3P
RXLQ-TAYCU,
RXYQ-TAYCU: A4P
YES
Explanation to users
∗
Use the document “Notice of Inspection Results” attached to spare part.
Hand the “Notice of Inspection Results” to user to ask
him/her to rectify the imbalance.
Be sure to explain user that “power supply
voltage imbalance” will occur and Daikin
accepts no responsibility for the imbalance.
Use equipment capable of constantly
recording power supply voltages (e.g.
Memory Hicoder) to record power
supply voltages between phases (R-S,
S-T, and R-T) for a period of
consecutive 1 week.
Power supply voltage imbalance
Even though power supply voltage
remains balanced when making
measurement, it often becomes
imbalanced during night-time (from
6:00 PM to 10:00 PM).
Even though the power
supply voltage is normal, the
error recurs.
<If voltage can be monitored>
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...