Field Setting from Outdoor Unit
SiUS341802E
129
Field Settings and Test Operation
[2-32]: Forced, all time, power consumption limitation operation (no external control adaptor is required to
perform power consumption limitation)
If the system always needs to be running under power consumption limitation conditions, this setting
activates and defines the level power consumption limitation that will be applied continuously. The level
is according to the table.
[2-34]: Indoor fan tap setting
Indoor fan speed limitation related to connection capacity and outdoor air temperature for energy saving.
∗
Indoor condition A: –1.5°C (–2.7°F) < Indoor air temperature – set temperature < 3°C (5.4°F)
∗
Indoor condition B: –1.5°C (–2.7°F)
≥
Indoor air temperature – set temperature, or
≥
3°C (5.4°F)
Value
[2-32]
Restriction reference
0 (default)
Function not active
1
Follows [2-30] setting
2
Follows [2-31] setting
Value
[2-34]
Indoor fan tap setting
0 (default)
Fan speed is limited to L tap when indoor units
capacity
≥
130%.
1
In heating mode, fan speed is limited to L tap
when indoor units capacity
≥
130%.
2
Fan speed follows a setting of the remote
controller (not limited by indoor units connection
capacity).
3
Fan speed is limited to L tap when outdoor air
temperature goes down to below 29.5°C (85.1°F)
and indoor condition A (
∗
). It returns to remote
controller setting when outdoor air temperature
goes up to over 32.5°C (90.5 °F) or indoor
condition B (
∗
).
4
Fan speed is limited to L tap when outdoor air
temperature goes down to below 23.5°C (74.3°F)
and indoor condition A (
∗
). It returns to remote
controller setting when outdoor air temperature
goes up to over 26.5°C (79.7°F) or indoor
condition B (
∗
).
5
Fan speed is limited to L tap when outdoor air
temperature goes down to below 19.3°C (66.7°F)
and indoor condition A (
∗
). It returns to remote
controller setting when outdoor air temperature
goes up to over 22.3°C (72.1°F) or indoor
condition B (
∗
).
6
Fan speed is limited to L tap when outdoor air
temperature goes down to below 29.5°C
(85.1°F). It returns to remote controller setting
when outdoor air temperature goes up to over
32.5°C (90.5°F).
7
Fan speed is limited to L tap when outdoor air
temperature goes down to below 23.5°C
(74.3°F). It returns to remote controller setting
when outdoor air temperature goes up to over
26.5°C (79.7°F).
8
Fan speed is limited to L tap when outdoor air
temperature goes down to below 19.3°C
(66.7°F). It returns to remote controller setting
when outdoor air temperature goes up to over
22.3°C (72.1°F).
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...