Field Settings from Remote Controller
SiUS341802E
99
Field Settings and Test Operation
1.5
Details of Field Settings for Indoor Unit
Filter Sign Setting
If switching the filter sign ON time, set as given in the table below.
Ultra Long Life Filter Sign Setting
When a Ultra long life filter is installed, the filter sign timer setting must be changed.
Filter Cleaning Sign Time
The filter cleaning sign display time can be changed.
FXTQ-TA
Selection of Thermistor
Select a thermistor to control room temperature.
When the unit is not equipped with an infrared presence/floor sensor:
The factory setting for the Second Code No. is
01
and room temperature is controlled by the suction air
thermistor and remote controller thermistor.
When the Second Code No. is set to
02
, room temperature is controlled by the suction air thermistor.
When the Second Code No. is set to
03
, room temperature is controlled by the remote controller thermistor.
FXTQ-TA
When the Second Code No. is set to
02
, room temperature is controlled by the remote sensor thermistor.
When the Second Code No. is set to
03
, room temperature is controlled by the remote controller thermistor.
Mode No.
First Code
No.
Second
Code No.
Standard
Filter
Long Life
Filter
Ultra Long Life
Filter
Contents
10 (20)
0
01
200 hrs.
2,500 hrs.
10,000 hrs.
Contamination Light
02
100 hrs.
1,250 hrs.
5,000 hrs.
Contamination Heavy
Mode No.
First Code No.
Second Code No.
Contents
10 (20)
1
01
Long Life Filter
02
Ultra Long Life Filter
Mode No.
First Code No.
Second Code No.
Contents (Light/Heavy)
10 (20)
1
01
2,500/1,250 hours
02
10,000/5,000 hours
Mode No.
First Code No.
Second Code No.
Contents
10 (20)
2
01
Remote controller thermistor and suction air
thermistor for indoor unit
02
Suction air thermistor for indoor unit
03
Remote controller thermistor
Mode No.
First Code No.
Second Code No.
Contents
10 (20)
2
01
—
02
Remote sensor thermistor
03
Remote controller thermistor
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...