Field Settings from Remote Controller
SiUS341802E
113
Field Settings and Test Operation
How to Select Operation Mode
Whether operation by remote controller will be possible or not for turning ON/OFF, controlling temperature or
setting operation mode is selected and decided by the operation mode given on the right edge of the table below.
: Factory setting
Do not select “timer operation possible by remote controller” if not using a remote controller. Operation by timer is
impossible in this case.
ON by remote
controller
(Unified ON by
central remote
controller)
OFF by remote
controller
(Unified OFF by
central remote
controller)
Temperature
control by
remote controller
Operation mode
setting by
remote controller
OFF by
remote
controller
Example
↓
Rejection
↓
Rejection
↓
Rejection
↓
Acceptance
↓
Acceptance
Control
mode is "1".
Control mode
Control by remote controller
Control mode
Operation
OFF
Temperature
control
Operation
mode setting
Unified operation,
individual operation
by central remote
controller, or
operation controlled
by timer
Unified OFF,
individual stop by
central remote
controller, or timer
stop
ON/OFF control
impossible by
remote controller
Rejection (Example)
Rejection (Example)
Rejection
(Example)
Rejection
Acceptance
0
Rejection
10
Acceptance
(Example)
Acceptance
(Example)
1 (Example)
Rejection
11
OFF control only
possible by remote
controller
Acceptance
Rejection
Acceptance
2
Rejection
12
Acceptance
Acceptance
3
Rejection
13
Centralized
Acceptance
Rejection
Acceptance
4
Rejection
14
Acceptance
Acceptance
5
Rejection
15
Individual
Acceptance
Rejection
Acceptance
6
Rejection
16
Acceptance
Acceptance
7
Rejection
17
Timer operation
possible by remote
controller
Acceptance
(During timer at ON
position only)
Rejection
(During timer at OFF
position only)
Rejection
Acceptance
8
Rejection
18
Acceptance
Acceptance
9
Rejection
19
Local remote controllers cannot set
temperature or operation mode when
the system is under centralized control
and
CENTRAL CONTROL
is displayed
on the screen.
BRC1E73
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...