Troubleshooting by Error Code
SiUS341802E
179
Service Diagnosis
2.6
Overload/Overcurrent/Lock of Indoor Fan Motor
Error Code
A6
Applicable
Models
FXMQ-M
Method of Error
Detection
This error is detected by detecting that the individual power supply for the fan turns OFF.
Error Decision
Conditions
When it is not detected that the individual power supply for the indoor fan turns ON while in
operation.
Supposed
Causes
Defective power supply for the indoor fan motor
Clogged drain piping
Actuation of the indoor unit safety device
Defective contact in the fan wiring circuit
Troubleshooting
Properly connect the cable.
NO
YES
YES
Is the
power supply
cable of the indoor
fan properly
connected?
NO
Is the fan
normally running?
Restart the fan.
Replace the indoor unit main
PCB (A1P).
It is supposed that the indoor
fan motor stops running due to
overload, overcurrent, or lock.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...