96
SM-Universal Encoder Plus User Guide
www.controltechniques.com
Issue Number: 6
Used to define the simulated encoder output in SSI mode, refer to Chapter
6.3
Used to define the simulated encoder output in SSI mode, refer to Chapter
6.3
If Pr
x.49
is set to one, Pr
x.04
, Pr
x.05
and Pr
x.06
are not updated. If this parameter is
zero, Pr
x.04
, Pr
x.05
and Pr
x.06
are updated normally.
The error status is provided so that the only one option error trip is required for each
Solutions Module slot. If an error occurs, the reason for the error is written to this
parameter and the drive may produce a ‘SLX.Er’ trip, where x is the slot number. A
value of zero indicates that the Solutions Module has not detected an error, a non-zero
value indicates that an error has been detected. (See Chapter 10
for the
meaning of the values in this parameter.) When the drive is reset, this parameter is
cleared for the relevant Solutions Module.
This Solutions Module includes a temperature monitoring circuit. If the PCB temperature
exceeds 90
°
C (94
°
C
V.03.02.00
or later), the drive fan is forced to operate at full speed
(for a minimum of 10s). If the temperature falls below 90
°
C (94
°
C
V.03.02.00
or later),
the fan can operate normally again. If the PCB temperature exceeds 100
°
C, the drive is
tripped and the error status is set to 74.
When operating with an Incremental plus commutation (absolute encoder), Ab.SErvo,
Fd.SErvo, Fr.SErvo or SC.SErvo this parameter should remain at default (Pr
x.46
= 1).
NOTE
x.47
SSI output turns
RW
Uni
US
Ú
0 to 16
Ö
16
Update rate: Background read
x.48
SSI output comms resolution
RW
Uni
US
Ú
0 to 32 bits
Ö
0
Update rate: Background read
x.49
Lock position feedback
RW
Bit
Ú
OFF (0) or On (1)
Ö
Update rate: Background write
x.50
Solutions Module error status
RO
Uni
NC
PT
Ú
0 to 255
Ö
Update rate: Background write
x.51
Solutions Module software sub-version
RO
Uni
NC
PT
Ú
0 to 99
Ö
Update rate: Write on power-up