Figure 5-6 Connector PL1
Table 5.1 Connector PL1 terminal descriptions
5.4
Power supply
The total user load of the drive and Solutions Modules if exceeded will result in a 24V
internal power supply overload, trip ‘PS.24V’.
The user load comprises of:
•
the drive’s digital outputs plus the SM-I/O Plus digital outputs
or
•
the drive’s main encoder supply plus the SM-Universal Encoder Plus encoder
supply
Example
If exceeding the user load:
•
the drive’s main encoder supply, SM-Universal Encoder Plus encoder supply,
drive’s digital output and SM-I/O Plus digital outputs
an external 24V >50W power supply will be required. The external 24V supply should
be connected to the drives control terminals 1 and 2.
5.5
Encoder shield connections
Shielding considerations are important for PWM drive installations due to the high
voltages and currents present in the output circuit with a very wide frequency spectrum,
typically from 0 to 20 MHz. Encoder inputs are liable to be disturbed if careful attention
is not given to managing the cable shields.
Terminal
Freeze inputs / Encoder outputs
Freeze
RS485
input
Freeze
+24V input
Ab output
Fd output
SSI output
Marker
output
1
Freeze
2
0V common
3
A
F
Data
4
A\
F\
Data\
5
B
D
Clock\
(input)
6
B\
D\
Clock
(input)
7
0V common
8
Freeze
Z
9
Freeze\
Z\
PL1
1
2
3
4
5
6
7
8
9
If the encoder will exceed the SM-Universal Encoder Plus and encoder supply (5V, 8V
>300mA, 15V >200mA), the encoder must be supplied externally without a power
supply connection to the module. Ensure the 0V connection is common between both
the SM-Universal Encoder Plus and the encoder.
NOTE
There should be no parallel connection of the external 24V supply and the encoder
supply from the drive.
NOTE