42
SM-Universal Encoder Plus User Guide
www.controltechniques.com
Issue Number: 6
6.1.4
Comms only, absolute encoders
The following parameter set-up should be followed when configuring a Comms only
absolute encoder.
Comms only absolute encoders, EndAt and SSI
Before power-up
Ensure:
•
Feedback device is connected
•
Drive secure disable is not given (terminal 31)
Power-up drive
Ensure:
•
Drive displays “inh”
•
If the drive trips refer to Chapter 10
Slot identification
Identify:
•
Identify slot and associated menu, 15, 16, or 17
Select Solutions
Module
Enter
:
•
Speed feedback selector Pr
3.26
1
: Slot 1,
2
: Slot 2,
3
: Slot 3
Set-up encoder
power supply
Enter
:
•
Encoder power supply Pr
x.13
0
: 5v,
1
: 8v,
2
:15v
Set-up encoder
type
Enter
:
•
Encoder Type Pr
x.15
8
(EndAt),
10
(SSI)
Set-up data
format
Enter:
•
SSI encoder format Pr
x.18
(
0
Gray code,
1
Binary format)
Auto
configuration
Enter:
•
EndAt
, It is possible for the drive to set-up Pr
x.09
, Pr
x.11
automatically see
Pr
x.18
Encoder comms
•
Encoder comms baud rate Pr
x.14
(EndAt, SSI)
•
Encoder comms resolution Pr
x.11
Where encoder comms is used for initial setting of the absolute position the
comms resolution in bits must be set correctly.
•
Encoder turns Pr
x.09
When an encoder with comms is used Pr
x.09
must contain the number of bits in
the comms message used to give the multi-turn information. For a single turn
comms encoder Pr
x.09
must be set to zero.
Error detection
Ensure
:
•
The required error detection is set-up in Pr
x.17
Initialisation
Ensure
:
•
Position feedback is initialised Pr
x.45
•
A re-initialise can be carried out enabling Pr
3.47
If SSI power supply bit monitor feature is enabled ensure that this has been configured
in encoder setup parameters; Pr
x.09
, Pr
x.11
.
NOTE