SM-Universal Encoder Plus User Guide
39
Issue Number: 6
www.controltechniques.com
6.1.1
Incremental encoders
The following parameter set-up should be followed when configuring an Incremental
Encoder.
Incremental Encoders, Ab, Fd, Fr, SC
Before power-
up
Ensure:
•
Feedback device is connected
•
Drive secure disable is not given (terminal 31)
Power-up drive
Ensure:
•
Drive displays “inh”
•
If the drive trips refer to Chapter 10
Slot
identification
Identify:
•
Identify slot and associated menu, 15, 16, or 17
Select
Solutions
Module
Enter
:
•
Speed feedback selector Pr
3.26
1
: Slot 1,
2
: Slot 2,
3
: Slot 3
Set-up
encoder power
supply
Enter
:
•
Encoder power supply Pr
x.13
0
: 5v,
1
: 8v,
2
:15v
Set-up
encoder type
Enter
:
•
Encoder Type Pr
x.15
0
(Ab),
1
(Fd),
2
(Fr),
6
(SC)
Set-up
encoder lines
per revolution
•
Equivalent lines per revolution Pr
x.10
Set according to encoder, see below for restrictions
•
Line per revolution divider Pr
x.46
The equivalent lines per revolution Pr
x.10
is divided by the value in Pr
x.46
. This can be used
when an encoder is used where the number of lines or sine waves per pole is not an integer e.g.
128.123 lines per rev = 128.123 in Pr
x.10
and 1000 in Pr
x.46
giving 128123/1000 = 128.123.
Set-up
encoder turns
•
Encoder turns Pr
x.09
Defines the maximum number of the revolution counter (when operating with an incremental
encoder) before it rolls over at zero e.g. if Pr
x.09
= 5, then Pr
x.04
counts up to 31 before rolling
over at zero.
Error detection
Ensure
:
•
The required error detection is set-up in Pr
x.17
Initialisation
Ensure
:
•
Position feedback is initialised Pr
x.45
•
A re-initialise can be carried out enabling Pr
3.47
Encoder
Pr x.10 Equivalent lines per revolution
Ab
Number of lines per revolution
Fd, Fr
Number of lines per revolution / 2
SC
Number of sine waves per revolution
When operating in servo mode with either of the above Incremental encoders a flux
alignment test (Pr
5.12
) is required at every power up in order to determine the phase
offset angle. The miminal movement flux alignment test can be set-up through Pr
5.14
to carry out the required test automatically at every power up.
NOTE