SM-Universal Encoder Plus User Guide
53
Issue Number: 6
www.controltechniques.com
The selection of which freeze input is used is dependent upon the value of Pr
x.38
. The
selection of the freeze inputs are as shown following. The default is 1 that corresponds
to only the 24V input.
The freeze input can take the form of either
1.
A 485 signal on terminals 8 and 9 of PL1
2.
A 24V signal on the freeze 24V input on terminal 1 of PL1
3.
A signal on the internal drive and slot freeze line generated by another Solution
Module.
Freeze data
Each time the freeze input to the Solutions Module becomes active the non-marker
position Pr
x.29
revolution counter Pr
x.30
position and Pr
x.31
fine position are stored
in Pr
x.35
freeze revolution counter Pr
x.36
freeze position and Pr
x.37
freeze fine
position and the freeze flag Pr
x.39
is set.
The freeze flag Pr
x.39
is not reset by the module and must be reset by the user, if not
reset no other freeze conditions will be stored.
When a freeze occurs on the Solutions Module the main drive slot can also be stored if
Pr
x.40
Freeze main drive other slots
is set to one.
6.6.2
Freeze input with SM-Applications
Whenever a SM-Applications and a SM-Universal Encoder Plus
are used, the freeze
input can be connected to either the SM-Universal Encoder Plus and Pr
x.40 Freeze
main drive other slots
set or connected to the SM-Applications.
Pr x.38
24V input
485 input
Drive / Slot bus input
0
No
No
No
1
Yes
No
No
2
No
Yes
No
3
Yes
Yes
No
4
No
No
Yes
5
Yes
No
Yes
6
No
Yes
Yes
7
Yes
Yes
Yes
For SM-Applications, also refer to Pr
90.47
and Pr
90.48
Enable freeze flag
.
NOTE