SM-Universal Encoder Plus User Guide
93
Issue Number: 6
www.controltechniques.com
The freeze input to the SM Universal Encoder Plus can take the following forms
•
A 485 signal through the encoder marker simulation output pins
•
A 24V signal on the freeze 24V input
•
A signal on the internal drive and slot freeze line generated by another Solutions
Module.
The selection of which mode used is dependent on the value of Pr
x.38
. The default is 1
that corresponds to only the 24V input to this Solutions Module. The values correspond
to the modes as described in the table below:
Each time the freeze input on the Solutions Module becomes active the non-marker
position (Pr
x.29
to Pr
x.31
) is stored in Pr
x.35
to Pr
x.37
and the freeze flag (Pr
x.39
)
is set. The freeze flag is not reset by the module and must be reset by the user. No other
freeze conditions will be trapped if the flag is set.
This parameter enables the Solutions Module to pass the freeze signal internally to the
drive and other slots so that when a freeze occurs on the Solutions Module the main
drive position and/or other slots can also be frozen.
When Pr
x.41
= 0 freeze occurs on the rising edge of the freeze input. When Pr
x.41
= 1
freeze occurs on the falling edge of the freeze input.
Value in Pr x.38
24V input
485 input
Drive/slot bus input
0
No
No
No
1
Yes
No
No
2
No
Yes
No
3
Yes
Yes
No
4
No
No
Yes
5
Yes
No
Yes
6
No
Yes
Yes
7
Yes
Yes
Yes
Modes 6 and 7 are only available with the drive software versions
01.07.00
onwards.
NOTE
x.39
Freeze flag
RW
Bit
NC
Ú
OFF (0) or On (1)
Ö
OFF (0)
Update rate: 250
µ
s write
x.40
Pass freeze to drive and other slots
RW
Bit
NC
US
Ú
OFF (0) or On (1)
Ö
OFF (0)
Update rate: Background read
x.41
Freeze invert
RW
Bit
US
Ú
OFF (0) or On (1)
Ö
OFF (0)
Update rate: Background read