Encoder initialisation will only occur when trips 1 through to 74 in Pr
x.50
, Solutions
Module error status are reset.
NOTE
Pr x.18
Auto-configuration enable\SSI binary format select
When a SC.HiPEr or SC.EndAt encoder is being used, the Solutions Module will interrogate the encoder on
power-up. If Pr
x.18
is set and the encoder type is recognised based on the information provided by the
encoder, the Solutions Module will set the encoder turns Pr
x.09
, the equivalent lines per revolution Pr
x.10
and
the encoder comms resolution Pr
x.11
for the encoder. If the encoder is recognised these parameters will all
become read only. If the encoder is not recognised, the Solutions Module will initiate a 7 trip to prompt the user
to enter the information. The Solutions Module should be able to auto-configure with any EndAt encoder where
the number of turns and lines per revolution are a power of 2, and the following Hiperface encoders: SCS 60/70,
SCM 60/70, SRS 50/60, SRM 50/60, SHS 170, LINCODER, SCS-KIT 101, SKS36, SKM36, SEK52, SEK53.
When operating with an SSI encoder, Pr
x.18
is used to set-up the data format: 0 = Gray
code and 1 = binary format.
NOTE
When using only the simulated encoder outputs from the SM-Universal Encoder Plus,
the error detection Pr
x.17
should be disabled to avoid Enc2 trips.
NOTE