76
Pn153
The speed regulator proportional gain 1
5~ 2000
100
%
All
Pn154
Speed regulator integral time constant of 1
5~ 2000
100
%
All
Pn155
The speed regulator proportional gain 2
5~ 2000
100
%
All
Pn156
Speed regulator integral time constant 2
5~ 2000
100
%
All
◢
Speed loop controller gain directly determine the response of the
speed control loop bandwidth, the mechanical system without vibration or noise, increase the speed loop
gain value, accelerated the response.
◢
Integral time constant is used to adjust the steady-state error compensation rate,
decrease the parameter values, reduce the speed control error, increase rigidity. Is too small easy to
cause vibration and noise.
number
name
value
range
the
default value
unit
apply
Pn157
▲
Simulation speed instruction
smoothing filtering time
1~500
1
0.1ms
S
◢
The set value, the greater the input analog response speed is slow, is beneficial to reduce
the high frequency noise, setting is smaller, the faster response speed, but will get big interference noise.
number
name
value range
the
default value
unit
apply
Pn158
The directive gain simulation speed
1~1500
300
r/min/V
S
◢
Analog speed reference input and the ratio between the actual speed motor. The range of input voltage
-
10 ~ 10 v. Formula: speed = * Pn158 input voltage. For example: when the input voltage of 10 v, if set to 300, the
corresponding rate of 10 * 300 = 3000 r/min.