52
hysteresis comparison. The setting of the difference is too small, the output signal cut-off frequency is
higher; The set value, the greater the cut-off frequency is small, but at the same time reduce the resolution
of the comparator. Example: booking speed is set to 100, difference set to 10.
OFF
100
90
110
ON
◢
Can be set up speed detection direction, in the following table
Pn023
The comparator
0
Positive &negative were detected
1
Testing only forward speed; Inversion, the signal is OFF
2
Only detect reverse speed; Forward, the signal is OFF
number
name
value range
the
default value
unit
apply
Pn024
reach
to
the
predetermined torque
0-300
100
%
All
Pn025
Reach a predetermined
torque hysteresis
comparison difference
0-300
5
%
All
Pn026
Reach the predetermined torque
direction
0-2
0
All
◢
When the motor running torque than the decision value set, the output port SigOut Treach will turn ON, or to OFF
◢
Can install torque detection direction, in the following table:
Pn026
The comparator
Speed
D-Value D-Value