50
Pn014
Torque overload 1 alarm
detection
time
0-800
80
100ms
All
Pn015
Overload 2 testing time
0-150
40
100ms
All
◢
Overload 1 alarm level refers to the overload overcurrent rated output current percentage, relative to
the motor overload capacity range between 0 and the maximum output current. Torque overload 1 the
overload capacity of the default value is 2 times, in the setting time, lasts for more than 2 times the output
torque, will perform overload 1 protection
◢
In a set time, the motor to allow the rated torque output ratio, will perform overload 2 protection
◢
If the overload level sets is greater than the corresponding internal/external torque limit, overload conditions may
not be met, the protection will not work
number
name
value range
the
default value
unit
apply
Pn016
▲
The molecular DA of
encoder divider output
1~63
1
All
Pn017
▲
1~63
1
All
◢
Encoder output, a electronic gear used for dividing the encoder pulse signal output. Frequency division value
must be satisfied: DA/DB > = 1. Encoder, for example, to line 2500, DA/DB crossover value = 25/8, then
after frequency division line number: 2500 / (DA/DB) = 2500 /
(25/8) = 800 line
number
name
value
range
the
default
value
unit
apply
Pn018
▲
Take the encoder output pulse
0-1
0
All
The denominator DB of
encoder divider output