94
Functions
k.air +030220981 rel. 1.2 - 01.12.2020
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
U
N
IT
Aa66 Unit setpoints - Return air fl ow - Setpoint
5000
LowLimVal
HiLimVal
m^3/h
R/W HR1152
PIV2662
Unit setpoints - Return air fl ow - Low limit value
3000
0
HiLimVal
m^3/h
R/W HR1153
PIV2663
Unit setpoints - Return air fl ow - High limit value
7000
LowLimVal
65535
m^3/h
R/W HR1154
PIV2664
Aa69 Unit setpoints - Return air fl ow - Setpoint
5000
LowLimVal
HiLimVal
m^3/h
R/W HR1155
PIV2665
Unit setpoints - Return air fl ow - Low limit value
3000
0
HiLimVal
m^3/h
R/W HR1156
PIV2666
Unit setpoints - Return air fl ow - High limit value
7000
LowLimVal
65535
m^3/h
R/W HR1157
PIV2667
Aa72 Scheduler: confi guration - Enabled
FALSE
0
1
-
R
CS064
BV64
Unit setpoints - Return air fl ow - Setpoint
5000
LowLimVal
HiLimVal
m^3/h
R/W HR1158
PIV2668
Unit setpoints - Return air fl ow - Low limit value
3000
0
HiLimVal
m^3/h
R/W HR1159
PIV2669
Unit setpoints - Return air fl ow - High limit value
7000
LowLimVal
65535
m^3/h
R/W HR1160
PIV2670
Aa75 Unit setpoints - Humidity - Cooling - Economy - Setpoint
60.0
LowLimVal
HiLimVal
%rh
R/W HR1161
AV2671
Unit setpoints - Humidity - Heating - Economy - Setpoint
40.0
LowLimVal
HiLimVal
%rh
R/W HR1162
AV2672
Unit setpoints - Humidity - Cooling - Economy - Low limit value
50.0
0.0
HiLimVal
%rh
R/W HR1163
AV2673
Unit setpoints - Humidity - Heating - Economy - Low limit value
35.0
0.0
HiLimVal
%rh
R/W HR1164
AV2674
Unit setpoints - Humidity - Cooling - Economy - High limit value
65.0
LowLimVal
100.0
%rh
R/W HR1165
AV2675
Unit setpoints - Humidity - Heating - Economy - High limit value
45.0
LowLimVal
100.0
%rh
R/W HR1166
AV2676
Aa78 Unit setpoints - Humidity - Cooling - Pre-comfort - Setpoint
55.0
LowLimVal
HiLimVal
%rh
R/W HR1167
AV2677
Unit setpoints - Humidity - Heating - Pre-comfort - Setpoint
45.0
LowLimVal
HiLimVal
%rh
R/W HR1168
AV2678
Unit setpoints - Humidity - Cooling - Pre-comfort - Low limit value
40.0
0.0
HiLimVal
%rh
R/W HR1169
AV2679
Unit setpoints - Humidity - Heating - Pre-comfort - Low limit value
30.0
0.0
HiLimVal
%rh
R/W HR1170
AV2680
Unit setpoints - Humidity - Cooling - Pre-comfort - High limit value
60.0
LowLimVal
100.0
%rh
R/W HR1171
AV2681
Unit setpoints - Humidity - Heating - Pre-comfort - High limit value
55.0
LowLimVal
100.0
%rh
R/W HR1172
AV2682
Aa81 Scheduler: confi guration - Enabled
FALSE
0
1
-
R
CS064
BV64
Unit setpoints - Humidity - Cooling - Comfort - Setpoint
50.0
LowLimVal
HiLimVal
%rh
R/W HR1173
AV2683
Unit setpoints - Humidity - Heating - Comfort - Setpoint
50.0
LowLimVal
HiLimVal
%rh
R/W HR1174
AV2684
Unit setpoints - Humidity - Cooling - Comfort - Low limit value
40.0
0.0
HiLimVal
%rh
R/W HR1175
AV2685
Unit setpoints - Humidity - Heating - Comfort - Low limit value
30.0
0.0
HiLimVal
%rh
R/W HR1176
AV2686
Unit setpoints - Humidity - Cooling - Comfort - High limit value
60.0
LowLimVal
100.0
%rh
R/W HR1177
AV2687
Unit setpoints - Humidity - Heating - Comfort - High limit value
55.0
LowLimVal
100.0
%rh
R/W HR1178
AV2688
Tab. 9.bh