82
Functions
k.air +030220981 rel. 1.2 - 01.12.2020
30220980_179_R01
100%
Dir
ect
Rev
erse
St
Heating
Cooling
Request
Min
0%
St
Max
100%
Reg_pr
Request
diff
Rev
erse
Dir
ec
t
Key
St
Set point
Reg_pr
Control probe
Max
Maximum modulating output value
Diff Diff erential
Min
Minimum modulating output value
Fig. 9.ak
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
A
U
X
ILI
ARY
_
R
E
G
UL
A
TI
ON
H001
Auxiliary Regulation 1 - Input selection
0
0
13
-
R/W HR1584
PIV3079
Auxiliary Regulation 1 - Output selection
0
0
1
-
R/W HR1585
PIV3080
H003
Auxiliary Regulation 1 - Dout: Error value
FALSE 0
1
-
R/W CS261
BV261
Auxiliary Regulation 1 - Modulating: Error value
0.0
0.0
100.0
-
R/W HR1586
AV3081
Auxiliary Regulation 1 - Enable selection
0
0
5
-
R/W HR1587
PIV3082
Auxiliary Regulation 1 - Enable selection: Manual enabling
FALSE 0
1
-
R/W CS262
BV262
H005
Auxiliary Regulation 1 - Setpoint selection
0
0
4
-
R/W HR1588
PIV3083
Auxiliary Regulation 1 - Regulation setpoint
20.0
- 9999.9 9999.9
-
R/W HR980
AV2502
Auxiliary Regulation 1 - Modulating: Low limit
0.0
0.0
100.0
-
R/W HR1589
AV3084
Auxiliary Regulation 1 - Dout: Diff erential
20.0
0.0
999.9
-
R/W HR1590
AV3085
Auxiliary Regulation 1 - Modulating: High limit
100.0
0.0
100.0
-
R/W HR1591
AV3086
Auxiliary Regulation 1 - Enable comfort auxiliary regulation
FALSE 0
1
-
R/W CS263
BV263
H007
Auxiliary Regulation 1 - Modulating: Kp
8.0
0.0
999.9
-
R/W HR1592
AV3087
Auxiliary Regulation 1 - Modulating: Integral time
120
0
999
-
R/W HR1593
PIV3088
Auxiliary Regulation 1 - Modulating: Derivative time
0
0
999
-
R/W HR1594
PIV3089
Auxiliary Regulation 1 - Modulating: Dead Band
0.0
0.0
999.9
-
R/W HR1595
AV3090
H009
Auxiliary Regulation 1 - Reverse mode
FALSE 0
1
-
R/W CS264
BV264
Auxiliary Regulation 1 - Cooling/Heating mode
FALSE 0
1
-
R/W CS265
BV265
Tab. 9.av
Example: electric heater management
The defrost heater is managed as an auxiliary control function, and must be enabled. The control probe in this case is the fresh
air probe. The On/Off heater features “direct- heating” activation, with the trend shown in the fi gure, while for the modulating
heater, the action depends on the PID parameters.
30220980_171_R01
OFF
St
ON
Ext_pr
Heating/direct
diff
Min
St
Max
100%
Ext_pr
Heating/direct
diff
Key
Ext_pr
Outside temperature probe
St
Set point
Diff Diff erential
Fig. 9.al