32
th-Tune (accessory)
k.air +030220981 rel. 1.2 - 01.12.2020
MESSAGES IN SMALL AREA
Message
D
escription
OFF by ALRM
OFF due to alarm
OFF by BMS
OFF from Building Management System
OFF by SCHD
OFF from scheduler
OFF by DIN
OFF from digital input
OFF by FAN
OFF due to fan alarm
OFF by COND
OFF due to alarm during start-up
STRT UP
Unit starting
SHUT DOWN
Shutting down
Tab. 5.d
OP
E
RA
TI
NG
M
OD
E
I
CON
Cooling
Heating
Automatic
/
Tab. 5.e
FAN
SP
EE
D
I
CON
Speed 1
Speed 2
Speed 3
Automatic speed
Tab. 5.f
TIME BAND NO.
1
2
3
4
5
6
Note:
the time band icon indicates:
1. when programming the time bands, the start time of the corresponding time band;
2. during operation: the current time band.
5.4
S
etting the time and day of the week
The current time and day of the week can only be set on the pGDE terminal.
Important:
setting the time and day of the week on the th Tune terminal HAS NO eff ect.
5.5
S
etting the time bands
See the paragraph at the end of the chapter. The time bands set on the th- Tune terminal are only eff ective when the k.Air
controller is in Comfort mode. In Economy mode, the unit set point depends on the set point confi gured on the corresponding
screen on the controller.
Example 1
Given the following conditions:
• unit in cooling mode with room temperature probe used as the control probe;
• time bands on pGDE not active;
• time bands on th-Tune set as follows:
Содержание k.Air
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 188: ...188 k air 030220981 rel 1 2 01 12 2020 Note...
Страница 189: ...189 k air 030220981 rel 1 2 01 12 2020 Note...
Страница 190: ...190 k air 030220981 rel 1 2 01 12 2020 Note...
Страница 191: ......