112
Parameter table
k.air +030220981 rel. 1.2 - 01.12.2020
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
U
N
IT
Ac62
High supply temperature threshold
32.0
0.0
40.0
°C
R/W HR1357
AV2865
High supply temperature alarm delay time at start up
999
0
65535
s
R/W HR1358
PIV2866
High supply temperature alarm delay time at unit in run mode
600
0
65535
s
R/W HR1359
PIV2867
Ac64
Low supply temp: proportional part
8.0
0.0
999.0
-
R/W HR1360
AV2868
Low supply temp: integral time
120
0
999
s
R/W HR1361
PIV2869
Ac66
Purge function - Time
10
0
999
min
R/W HR1949
PIV3972
Purge function - Automatic mode
0
0
3
-
R/W HR1950
PIV3973
Purge function - Start hour
0
0
23
h
R/W HR1951
PIV3974
Purge function - Start minute
0
0
59
min
R/W HR1952
PIV3975
Ac68
FALSE=forced off ; TRUE=manual activation
FALSE
0
1
-
R/W CS230
BV230
FALSE=forced off ; TRUE=manual activation
FALSE
0
1
-
R
CS230
BV230
Enabling of the regulation probe error status during the off state
FALSE
0
1
-
R/W CS231
BV231
Ac70
Fresh air damper request in case of regulation probe error: modulating
0.0
0.0
100.0
%
R/W HR1362
AV2870
Fresh air damper request in case of regulation probe error: on/off 0
0
100
%
R/W HR1363
PIV2871
Bypass damper request in case of regulation probe error: modulating 0.0
0.0
100.0
%
R/W HR1364
AV2872
Thermal wheel request in case of regulation probe error: modulating
0.0
0.0
100.0
%
R/W HR1365
AV2873
Bypass damper request in case of regulation probe error: on/off 0
0
100
%
R/W HR1366
PIV2874
Mixing damper request in case of regulation probe error
0.0
0.0
100.0
%
R/W HR1367
AV2875
Mixing damper request in case of regulation probe error
0
0
100
%
R/W HR1368
PIV2876
Exhaust damper request in case of regulation probe error
0.0
0.0
100.0
%
R/W HR1369
AV2877
Exhaust damper request in case of regulation probe error
0
0
100
%
R/W HR1370
PIV2878
Ac72
Supply damper request in case of regulation probe error
0.0
0.0
100.0
%
R/W HR1371
AV2879
Supply damper request in case of regulation probe error
0
0
100
%
R/W HR1372
PIV2880
Return damper request in case of regulation probe error
0.0
0.0
100.0
%
R/W HR1373
AV2881
Return damper request in case of regulation probe error
0
0
100
%
R/W HR1374
PIV2882
Main coil request in case of regulation probe error
0.0
0.0
100.0
%
R/W HR1375
AV2883
PreHeating coil request in case of regulation probe error
50.0
0.0
100.0
%
R/W HR1376
AV2884
PostHeating coil request in case of regulation probe error
50.0
0.0
100.0
%
R/W HR1377
AV2885
Ac74
Supply fan speed request in case of regulation probe error
0
0
3
%
R/W HR1378
PIV2886
Supply fan speed request in case of regulation probe error
0.0
0.0
100.0
%
R/W HR1379
AV2887
Supply fan speed request in case of regulation probe error
0
0
100
%
R/W HR1380
PIV2888
Supply fan speed request in case of regulation probe error
0
0
3
%
R/W HR1381
PIV2889
Return fan speed request in case of regulation probe error
0.0
0.0
100.0
%
R/W HR1382
AV2890
Supply fan speed request in case of regulation probe error
0
0
100
%
R/W HR1383
PIV2891
Compressor request in case of regulation probe error: BLDC
0.0
0.0
100.0
%
R/W HR1384
AV2892
Compressor request in case of regulation probe error: On/off 0
0
100
%
R/W HR1385
PIV2893
Humidifi cation request in case of regulation probe error
0.0
0.0
100.0
%
R/W HR1386
AV2894
IEC: request in case of regulation probe error
0.0
0.0
100.0
%
R/W HR1387
AV2895
Ac76
Enable thTune management
FALSE
0
1
-
R/W CS232
BV232
Ac78
Enable function that allows th-Tune to keep unit ON for 'thTunePartyDT' FALSE
0
1
-
R/W CS233
BV233
Time to keep the unit ON after th-Tune disables the scheduler/time-
band which was OFF (minutes)
1
0
360
-
R/W HR1388
PIV2896
Ac80
Auxiliary regulation type
0
0
4
-
R/W HR1389
PIV2897
Enable on/off request by BMS
-
0
1
-
R/W CS234
BV234
OnOff by k.water enabling
FALSE
0
1
-
R/W CS235
BV235
Ac82
BMS Offl
ine alarm management (0: Disabled; 1: Only Warning; 2:
Alarm; 3: Alarm with timeout)
0
0
3
-
R/W HR1390
PIV2898
BMS Offl
ine alarm timeout [s]
120
0
999
s
R/W HR1391
PIV2899
Ac84
pGDx: Main variable selection
1
1
16
-
R/W HR1392
PIV2900
pGDx: Second variable selection
11
1
16
-
R/W HR1393
PIV2901
Ac86
Enable VDI management
FALSE
0
1
-
R/W CS236
BV236
VDI high saturation humidity startup enabled
FALSE
0
1
-
R/W CS237
BV237
Ac97
Set wipe memory
-
0
1
-
R/W HR1394
PIV2902
Ac99
Drive type (0: Internal public volume; 1: USB pendrive)
-
0
1
-
R/W HR1015
PIV2537
HR1018
IV2539
HR1020
IV2540
HR1022
IV2541
HR1024
IV2542
HR1026
IV2543
HR1028
IV2544
HR1030
IV2545
HR1032
IV2546
HR1034
IV2547
HR1036
IV2548
HR1038
IV2549
-
-