135
Parameter table
k.air +030220981 rel. 1.2 - 01.12.2020
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
I
NFOR
M
A
TI
ONS
Qz 21 Fan status (working mode, errors) - Working status defi nes
current working conditions
-
0
65535
-
R
IR33 8
PIV3 719
Fan status (working mode, errors) - Working status code
-
0
9
-
R
IR33 9
PIV3 720
Qz 24 Fan speed informations - Actual speed [rpm] of the Zhiel-Abegg fan -
0
9999
-
R
IR34 0
PIV3 721
Fan electrical informations - DC link voltage (V)
-
0
9999
-
R
IR34 1
PIV3 722
Fan electrical informations - Supply voltage (peak voltage)
-
0
65535
-
R
IR34 2
PIV3 723
Fan speed informations - Maximum set speed
-
0
9999
-
R
IR34 3
PIV3 724
Fan speed informations - Minimum set speed
-
0
65535
-
R
IR34 4
PIV3 725
Fan electrical informations - Motor input power (W)
-
0
65535
-
R
IR34 5
PIV3 726
Qz 27 Fan electrical informations - Electronics temperature (°C)
-
-999.9
999.9
-
R
IR34 6
AV37 27
Fan electrical informations - IGBT temperature (°C)
-
-999.9
999.9
-
R
IR34 7
AV37 28
Fan electrical informations - MCU temperature
-
-999.9
999.9
-
R
IR34 8
AV37 29
Fan electrical informations - Motr temperature (°C)
-
-999.9
999.9
-
R
IR34 9
AV37 30
Qz 30 Fan alarms - Error status defi nes errors currently detected
-
0
65535
-
R
IR35 0
PIV3 731
Fan alarms - Error status bit 10: peak current error
-
0
1
-
R
DI68 3
BV11 41
Fan alarms - Error status bit 9: Motor blocked
-
0
1
-
R
DI68 4
BV11 42
Fan alarms - Error status bit 8: Hall sensor error
-
0
1
-
R
DI68 5
BV11 43
Fan alarms - Error status bit 7: Not used, reserved for PMblue etc. -
0
1
-
R
DI68 6
BV11 44
Fan alarms - Error status bit 6 : Line Fault
-
0
1
-
R
DI68 7
BV11 45
Fan alarms - Error status bit 5: Uin Low (from FW 10)
-
0
1
-
R
DI68 8
BV11 46
Fan alarms - Error status bit 4: Uin High (from FW 10)
-
0
1
-
R
DI68 9
BV11 47
Fan alarms - Error status: bit 3: UZK LO
-
0
1
-
R
DI69 0
BV11 48
Fan alarms - Error status: bit 2: UZK HI
-
0
1
-
R
DI69 1
BV11 49
Fan alarms - Error status bit 1: Earth to GND fault
-
0
1
-
R
DI69 2
BV11 50
Fan alarms - Error status bit 0: IGBT fault
-
0
1
-
R
DI69 3
BV11 51
Fan status (working mode, errors) - Working status defi nes
current working conditions
-
0
65535
-
R
IR35 1
PIV3 732
Fan status (working mode, errors) - Working status code
-
0
9
-
R
IR35 2
PIV3 733
Qz 33 Device info - Firmware release (high part)
-
0
9
-
R
IR35 3
PIV3 734
Device info - Firmware release (low part)
-
0
9
-
R
IR35 4
PIV3 735
Device info - Working hours of the unit
-
-32768
32767
-
R
IR35 5
IV37 36
Lists of variables of the device not managed by default
-
0
8
-
R
IR35 6
IV37 37
Alarm code read from device
-
0
99
-
R
IR35 7
PIV3 738
Qz 93 Actual day
-
0
99
d
R
IR35 8
PIV3 739
Actual month
-
0
99
mo nth R
IR35 9
PIV3 740
Actual year
-
0
99
y
R
IR36 0
PIV3 741
cpCO real time clock
-
0
99
-
R
IR36 1
PIV3 742
cpCO real time clock
-
0
99
-
R
IR36 2
PIV3 743
cpCO real time clock
-
0
99
-
R
IR36 3
PIV3 744
Saving of last day before blackout
-
0
99
d
R
IR36 4
PIV3 745
Saving of last month before blackout
-
0
99
mo nth R
IR36 5
PIV3 746
Saving of last year before blackout
-
0
99
y
R
IR36 6
PIV3 747
Saving of last hour before blackout
-
0
99
h
R
IR36 7
PIV3 748
Saving of last minute before blackout
-
0
99
min
R
IR36 8
PIV3 749
Saving of last second before blackout
-
0
99
s
R
IR36 9
PIV3 750
Number of days since the last blackout
-
0
999
d
R
IR37 0
PIV3 751
Number of hours since the last blackout
-
0
99
h
R
IR37 1
PIV3 752
Numbers of minutes since the last blackout
-
0
99
min
R
IR37 2
PIV3 753
Qz 96 Last polling loop time (ms)
-
0
999999
ms
R
IR37 3
PIV3 754
Number of Polling loops
-
0
999999
-
R
IR37 5
PIV3 755
Qz 99 Absolute number of writings in retain memory during the entire
device life
-
0
999999
-
R
IR37 7
PIV3 756
Program speed in ms
-
0
9999
ms
R
IR37 9
PIV3 757
Program speed in CyclePerSecond
-
- 99999.9
99999.9
-
R
IR38 0
AV37 58
Tab. 10.p
Notes:
• the values indicated by “---” are not signifi cant or have not been set;
• the values indicated by “...” may diff er depending on the confi guration, and the options are shown on the user terminal;
• an entire row of “...” indicates similarly parameters that are repeated;
• Modbus variables: HR (holding registers), DI (Discrete inputs), IR (input registers), CS (Coils);
Содержание k.Air
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 188: ...188 k air 030220981 rel 1 2 01 12 2020 Note...
Страница 189: ...189 k air 030220981 rel 1 2 01 12 2020 Note...
Страница 190: ...190 k air 030220981 rel 1 2 01 12 2020 Note...
Страница 191: ......