50
Functions
k.air +030220981 rel. 1.2 - 01.12.2020
F
resh air damper
Mixing damper
C
ontrol
Modulating
On/off or absent
Fresh air damper opens to the maximum (settable limit) when the unit is ON
If there is no mixing damper, the fresh air damper goes into freecooling (main temperature
control) or air quality control mode, or both.
When frost prevention is active, the fresh air damper progressively closes, while the mixing
damper remains closed
If frost protection is active, the fresh air damper closes and, if the mixing damper is fi tted, the
unit enters recirculation mode, with the fans on
On/off
Modulating
Fresh air damper opens when the unit is ON and the mixing damper opens to the minimum
(settable limit)
Mixing damper goes into freecooling or air quality control mode, or both.
When frost prevention is active, the mixing damper progressively closes.
If frost protection is active, the fresh air damper closes and the mixing damper opens to the
maximum (settable limit)
Modulating
Modulating
Fresh air and mixing dampers, in sync, go into freecooling (main temperature control) or air
quality control mode, or both.
When frost prevention is active, the fresh air damper progressively closes, while the mixing
damper progressively opens.
If frost protection is active, the fresh air damper closes and the mixing damper opens.
Tab. 9.a
R
if
D
escription
D
ev
Min Max
UoM
D
ir
Modbus
BAC
net
DA
M
P
E
RS
Ca01
Damper opening time
120
0
65535 s
R/W HR1639
PIV3134
Ca03
Enable air quality regulation for fresh air OR mixing damper
FALSE 0
1
-
R/W CS289
BV289
Air Quality - Dampers PID parameters - Proportional gain
1.0
0.0
999.9
-
R/W HR1640
AV3135
Air Quality - Dampers PID parameters - Integral time
60
0
999
-
R/W HR1641
PIV3136
Ca06
Fresh air damper - Minimum regulation value
0.0
0.0
100.0
%
R/W HR1642
AV3137
Fresh air damper - Maximum regulation value
100.0
0.0
100.0
%
R/W HR1643
AV3138
Ca09
Mixing air damper - Minimum regulation value
0.0
0.0
100.0
%
R/W HR1644
AV3139
Mixing air damper - Maximum regulation value
100.0
0.0
100.0
%
R/W HR1645
AV3140
Ca12
Enable dampers regulation in case of FreeCooling/FreeHeating
FALSE 0
1
-
R/W CS290
BV290
Tab. 9.b
9.1.3
B
ypass damper
Operation of the bypass damper depends greatly on whether a cross- fl ow heat recovery unit is fi tted. This may be on/off or
modulating, and has the purpose of allowing freecooling and, for modulating dampers, limiting heat recovery capacity for pre-
cise air temperature control.
Below is a summary of the functions available based on the type of damper
B
ypass damper
C
ontrol
On/off
The damper is activated by checking the outside air and return/room temperature conditions
Modulating
The damper is only controlled after checking the outside air and return/room temperature conditions
Modulation is managed by the main temperature control function
Tab. 9.c
R
if
D
escription
D
ev
Min Max
UoM
D
ir
Modbus
BAC
net
HE
A
T
R
E
CO
VE
RY
E001
Heat recovery delta for bypass damper in cooling mode
4.0
-99.9 99.9
K
R/W HR1458
AV2966
Heat recovery delta for bypass damper in heating mode
4.0
-99.9 99.9
K
R/W HR1459
AV2967
Tab. 9.d
Note:
when the unit is Off , the bypass damper will be open.
9.2
A
ctivation
The k.air software enables the unit to be switched on only if all of the enabled commands are set to ON (from pGDE/thTune, BMS,
digital input, scheduler). When the unit is switched on, a procedure is activated to verify all of the safety conditions and activate
the devices following a certain sequence; the dampers are opened 100% and the unit will complete the warm-up procedure,
if enabled, before switching to steady state operation, in the active control mode.