Functions
k.air +030220981 rel. 1.2 - 01.12.2020
9.26
P
robe error management
The k.Air controller software features specifi c device management and/or control functions in the event of probe errors.
Normally, the device or function associated with a probe alarm is deactivated, so as to avoid control being based on inaccurate
values, however in some special cases the devices can be managed by setting a fi xed percentage, so as to allow the unit to
continue operating, albeit without guaranteeing optimal control.
There are two special cases:
1. fan control in the event of air quality/pressure probe error: the value can be set on screen Bb01 (supply fan) and Bc01 (return fan).
2. auxiliary control in the event of an error on the corresponding probe the value can be set on screen H02.
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
A
U
X
ILI
ARY
_
R
E
G
UL
A
TI
ON
H003
Auxiliary Regulation 1 - Dout: Error value
FALSE 0
1
-
R/W CS261
BV261
Auxiliary Regulation 1 - Modulating: Error value
0.0
0.0
100.0
-
R/W HR1586
AV3081
Auxiliary Regulation 1 - Enable selection
0
0
5
-
R/W HR1587
PIV3082
Auxiliary Regulation 1 - Enable selection: Manual enabling
FALSE 0
1
-
R/W CS262
BV262
H013
Auxiliary Regulation 2 - Dout: Error value
FALSE 0
1
-
R/W CS268
BV268
Auxiliary Regulation 2 - Modulating: Error value
0.0
0.0
100.0
-
R/W HR1599
AV3094
Auxiliary Regulation 2 - Enable selection
0
0
5
-
R/W HR1600
PIV3095
Auxiliary Regulation 2 - Enable selection: Manual enabling
FALSE 0
1
-
R/W CS269
BV269
H023
Auxiliary Regulation 3 - Dout: Error value
FALSE 0
1
-
R/W CS275
BV275
Auxiliary Regulation 3 - Modulating: Error value
0.0
0.0
100.0
-
R/W HR1613
AV3108
Auxiliary Regulation 3 - Enable selection
0
0
5
-
R/W HR1614
PIV3109
Auxiliary Regulation 3 - Enable selection: Manual enabling
FALSE 0
1
-
R/W CS276
BV276
H033
Auxiliary Regulation 4 - Dout: Error value
FALSE 0
1
-
R/W CS282
BV282
Auxiliary Regulation 4 - Modulating: Error value
0.0
0.0
100.0
-
R/W HR1627
AV3122
Auxiliary Regulation 4 - Enable selection
0
0
5
-
R/W HR1628
PIV3123
Auxiliary Regulation 4 - Enable selection: Manual enabling
FALSE 0
1
-
R/W CS283
BV283
Tab. 9.bg
In addition, control probe errors are managed specifi cally, involving various devices. In this case, the following can be selected:
• shut the unit down (Off ), or switch off all of the devices after the corresponding delay times (post ventilation, damper closing
time, compressor times).
• set a fi xed percentage of operation for each device.
These values are available (if the function is enabled) on screens Ac70, Ac72, Ac74. In this case, all of the alarms still remain active.
It is also possible to enable this function even when the unit is Off , in which case only the water coils are forced to the set per-
centage for frost protection, as otherwise this cannot be correctly controlled. This function has priority over any other special
functions.
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
U
N
IT
Ac70
Fresh air damper request in case of regulation probe error: modulating
0.0
0.0
100.0
%
R/W HR1362
AV2870
Fresh air damper request in case of regulation probe error: on/off 0
0
100
%
R/W HR1363
PIV2871
Bypass damper request in case of regulation probe error: modulating
0.0
0.0
100.0
%
R/W HR1364
AV2872
Thermal wheel request in case of regulation probe error: modulating
0.0
0.0
100.0
%
R/W HR1365
AV2873
Bypass damper request in case of regulation probe error: on/off 0
0
100
%
R/W HR1366
PIV2874
Mixing damper request in case of regulation probe error
0.0
0.0
100.0
%
R/W HR1367
AV2875
Mixing damper request in case of regulation probe error
0
0
100
%
R/W HR1368
PIV2876
Exhaust damper request in case of regulation probe error
0.0
0.0
100.0
%
R/W HR1369
AV2877
Exhaust damper request in case of regulation probe error
0
0
100
%
R/W HR1370
PIV2878
Ac72
Supply damper request in case of regulation probe error
0.0
0.0
100.0
%
R/W HR1371
AV2879
Supply damper request in case of regulation probe error
0
0
100
%
R/W HR1372
PIV2880
Return damper request in case of regulation probe error
0.0
0.0
100.0
%
R/W HR1373
AV2881
Return damper request in case of regulation probe error
0
0
100
%
R/W HR1374
PIV2882
Main coil request in case of regulation probe error
0.0
0.0
100.0
%
R/W HR1375
AV2883
PreHeating coil request in case of regulation probe error
50.0
0.0
100.0
%
R/W HR1376
AV2884
PostHeating coil request in case of regulation probe error
50.0
0.0
100.0
%
R/W HR1377
AV2885
Ac74
Supply fan speed request in case of regulation probe error
0
0
3
%
R/W HR1378
PIV2886
Supply fan speed request in case of regulation probe error
0.0
0.0
100.0
%
R/W HR1379
AV2887
Supply fan speed request in case of regulation probe error
0
0
100
%
R/W HR1380
PIV2888
Supply fan speed request in case of regulation probe error
0
0
3
%
R/W HR1381
PIV2889
Return fan speed request in case of regulation probe error
0.0
0.0
100.0
%
R/W HR1382
AV2890
Supply fan speed request in case of regulation probe error
0
0
100
%
R/W HR1383
PIV2891
Compressor request in case of regulation probe error: BLDC
0.0
0.0
100.0
%
R/W HR1384
AV2892
Compressor request in case of regulation probe error: On/off 0
0
100
%
R/W HR1385
PIV2893
Humidifi cation request in case of regulation probe error
0.0
0.0
100.0
%
R/W HR1386
AV2894
IEC: request in case of regulation probe error
0.0
0.0
100.0
%
R/W HR1387
AV2895
Tab. 9.a