116
Parameter table
k.air +030220981 rel. 1.2 - 01.12.2020
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
FANS
Ba18
Enable night minimum ventilation
FALSE
0
1
-
R/W CS248
BV248
Night minimum ventilation: starting hour
22
0
23
h
R/W HR1501
PIV3002
Night minimum ventilation: starting minutes
0
0
59
min
R/W HR1502
PIV3003
Night minimum ventilation: ending hour
6
0
23
h
R/W HR1503
PIV3004
Night minimum ventilation: ending minutes
0
0
59
min
R/W HR1504
PIV3005
Ba21
Night minimum ventilation request
50.0
0.0
100.0
-
R/W HR1505
AV3006
Priority between minimum ventilation and night free cooling (FALSE:
minimum ventilation; TRUE: free cooling)
FALSE
0
1
-
R/W CS249
BV249
Ba24
Fan K factor for air fl ow calculations
100.0
0.0
99999.0
-
R/W HR1506
AV3007
Ba27
Fan fi xed speed request
30.0
0.0
100.0
%
R/W HR1507
AV3008
(0 = SPEED1; 1= SPEED2; 2= SPEED 3) Three speed fan
request in fi xed speed regulation
2
0
2
-
R/W HR1508
PIV3009
3 speeds fan type enabled
-
0
1
-
R
DI704
BV1162
Three speed fan limit 1
33.0
0.0
FansThree-
Speed2
%
R/W HR1509
AV3010
3 speeds fan type enabled
-
0
1
-
R
DI704
BV1162
Three speed fan limit 2
66.0
FansThree-
Speed1
FansThree-
Speed3
%
R/W HR1510
AV3011
3 speeds fan type enabled
-
0
1
-
R
DI704
BV1162
Three speed fan limit 3
100.0
FansThree-
Speed2
100.0
%
R/W HR1511
AV3012
Ba30
Fan air quality minimum request
10.0
0.0
100.0
%
R/W HR1512
AV3013
Ba33
Fan temperature regulation PID parameters - Proportional gain
8.0
-999.9
999.9
-
R/W HR1513
AV3014
Fan temperature regulation PID parameters - Integral time
120
0
65535
-
R/W HR1514
PIV3015
Ba36
Proportional gain
8.0
0.0
999.9
-
R/W HR1515
AV3016
Integral time
120
0
999
-
R/W HR1516
PIV3017
Dead band
0.0
-999.9
999.9
-
R/W HR1517
AV3018
Supply air fl ow deadband
0.0
0.0
3000.0
m^3/h
R/W HR1518
AV3019
Dead band
0.0
-999.9
999.9
-
R/W HR1517
AV3018
Bb01
Supply fan request in case of air pressure probe error
25.0
0.0
100.0
-
R/W HR1563
AV3063
Bb03
Minimum fan speed during antifreeze
10.0
0.0
100.0
%
R/W HR1564
AV3064
Bb06
Supply fan: Minimum regulation value
0.0
0.0
100.0
%
R/W HR1896
AV3376
Supply fan: Maximum regulation value
100.0
0.0
100.0
%
R/W HR1897
AV3377
Bb09
Automatically generated - Time in [s]for a positive change for Ebm-
papst fan
10
0
625
s
R/W HR1565
PIV3065
Automatically generated - Time in [s] for a negative change of set
value for Ebmpapst fan
10
0
625
s
R/W HR1566
PIV3066
Automatically generated - Preferred running direction (FALSE: left;
TRUE: right) for Ebmpapst fan
FALSE
0
1
-
R/W CS254
BV254
Bb12
Settings of the emergency function - Enable emergency function
(FALSE: Inactive; TRUE: Active; ) for Ebmpapst fan
FALSE
0
1
-
R/W CS255
BV255
Fan speed in emergency in rpm
0
0
MaxSpeed
-
R/W HR1567
IV3067
Settings of the emergency function - Time in ms before entering in
emergency mode for Ebmpapst fan
5000
0
65535
ms
R/W HR1569
PIV3068
Bb15
Serial interface settings (Address, baudrate, parity confi guration) -
Network address for Ebmpapst fan
30
0
999999
-
R/W HR1570
PIV3069
Serial interface settings (Address, baudrate, parity confi guration) -
Enable change address procedure
-
0
1
-
R/W CS256
BV256
Automatically generated - 0:Check condition;1: Write new addr.;
2: Reboot fan fi rmware; 3: Wait offl
ine; 4: Reset communication and
wait online status;5:Reset procedure;
-
0
9
-
R
IR515
PIV3829
Bb18
Serial interface settings (Address, baudrate, parity confi guration) -
Baudrate [bps] for the communication with the fan. (0=1200, 1=2400,
2=4800, 3=9600, 4=19200, 5=38400, 6=57600, 7=115200)
4
0
9
-
R/W HR1572
PIV3070
Serial interface settings (Address, baudrate, parity confi guration) -
Parity confi guration ready to be sent via modbus (0 = 8E1; 1 = 8O1;
2= 8N2; 3 = 8N1)
2
0
3
-
R/W HR1573
PIV3071
Serial interface settings (Address, baudrate, parity confi guration)
- Enable change communication interface fan settings (baudrate,
parity, stop bit)
-
0
1
-
R/W CS257
BV257
Automatically generated - 0:Idle; 1: Write password; 2:Write parame-
ters; 3:Send adopt parameters; 4:Wait offl
ine; 5:Reset procedure;
-
0
9
-
R
IR516
PIV3830
Bb21
Serial interface settings (Address, baudrate, parity confi guration) -
Frame timeout (ms)
500
0
9999
ms
R/W HR1574
PIV3072
Serial interface settings (Address, baudrate, parity confi guration) -
Command delay time (ms)
4
0
9999
ms
R/W HR1576
PIV3073
Bb24
Fan control mode parameetrs (Speedtype, ramp up/down time, ecc..)
- Ramp up timing for ZiehlAbegg fan [s]
0
0
625
-
R/W HR1578
PIV3074
Fan control mode parameetrs (Speedtype, ramp up/down time, ecc..)
- Ramp down timing for ZiehlAbegg fan [s]
0
0
625
-
R/W HR1579
PIV3075
Fan control mode parameetrs (Speedtype, ramp up/down time, ecc..)
- Running direction (FALSE=clockwise, TRUE=counter-clockwise)
FALSE
0
1
-
R/W CS258
BV258
Содержание k.Air
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 188: ...188 k air 030220981 rel 1 2 01 12 2020 Note...
Страница 189: ...189 k air 030220981 rel 1 2 01 12 2020 Note...
Страница 190: ...190 k air 030220981 rel 1 2 01 12 2020 Note...
Страница 191: ......