61
Functions
k.air +030220981 rel. 1.2 - 01.12.2020
9.8
S
et point compensation with outside air probe
The control set point can be adjusted according to the temperature read by the outside air probe, adding or subtracting an
off set. The off set is proportional to the deviation of the outside temperature from the start compensation threshold. The confi -
guration parameters are diff erent for heating and cooling mode.
The fi gure shows an example of a compensation in cooling mode with supply temperature control.
30220980_161_R01
Max_comp_offs
0%
Cool_thr
Ext_T
Supply set offset
delta
Key
Supply set off set
Supply set point off set
Max_comp_off s
Maximum compensation off set
Ext_T
Outside temperature
Cool_thr
Cooling threshold
delta
Diff erential
Fig. 9.q
Note:
the function requires an outside air temperature probe: if there is an alarm on this probe, the function is disabled.
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
U
N
IT
Aa84 Enable setpoint compensation by external temperature
FALSE 0
1
-
R/W CS195
BV195
Aa87 Cooling: external temperature compensation threshold
25.0
-50.0
90.0
°C
R/W HR1179
AV2689
Cooling: external temperature compensation delta
7.0
-30.0
30.0
°C
R/W HR1180
AV2690
Cooling: maximum compensation off set
2.0
-20.0
10.0
°C
R/W HR1181
AV2691
Aa90 Heating: external temperature compensation threshold
0.0
-50.0
90.0
°C
R/W HR1182
AV2692
Heating: external temperature compensation delta
-8.0
-30.0
30.0
°C
R/W HR1183
AV2693
Heating: maximum compensation off set
-2.0
-20.0
10.0
°C
R/W HR1184
AV2694
Tab. 9.p
9.9
C
oils
k.air can manage up to three coils, called preheating, main and reheating. Each of these has diff erent characteristics and requi-
rements. The table below summarises the main features, while the details are described in the chapters corresponding to each
control function.
C
oil
Mode
Type
C
ontrol
Preheating
Heating only
1. Modulating water coil
• Main temperature control in heating mode
• Frost
protection
• Minimum temperature limit for adiabatic humidifi cation
2. Progressive steps
3. Binary steps
4. Capacity modulation
(multi-stage)
5. Modulating water coil, 3 position
Main
Heating only
Cooling only
Mixed (reverse cycle)
1. Modulating water coil
• Main temperature control in cooling mode as the only active
device
• Main temperature control in heating mode as stage after prehe-
ating, where featured.
• Dehumidifi
cation
control
• Frost
protection
• Minimum temperature limit for adiabatic humidifi cation
2. Progressive steps
3. Binary steps
4. Capacity modulation
(multi-stage)
5. Modulating water coil, 3 position
6. Integrated direct expansion
7. Direct expansion with μChiller
Reheating
Heating only
1. Modulanti ad acqua
• Main temperature control in heating mode as the last stage
• Reheating during dehumidifi cation
• Frost
protection
• Minimum temperature limit for adiabatic humidifi cation
2. Step progressivi
3. Step binari
4. Modulazione di potenza
(multistadio)
5. Modulanti ad acqua 3 punti
Tab. 9.q
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
U
N
IT
Ac08
PreHeating coil type
0
0
5
-
R/W HR1296
PIV2804
Main coil type
0
0
7
-
R/W HR1297
PIV2805
PostHeating coil type
0
0
5
-
R/W HR1298
PIV2806
Tab. 9.r