64
Functions
k.air +030220981 rel. 1.2 - 01.12.2020
Direct expansion coil with μChiller management
The uChiller direct expansion architecture involves modular architecture, with the refrigerant circuit managed by an external
uChiller controller, connected via the Fieldbus serial port available on k.air. This allows to the refrigeration unit to be expanded
to include two circuits with two compressors each, either on/off or BLDC. Unlike integrated direct expansion management, the
source heat exchanger is managed externally from the air handling unit, via a condensing/evaporation signal.
See the chapter “Direct expansion with uChiller” for more information.
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
CO
IL
S
Da01
Main coil confi guration
2
0
2
-
R/W HR1654
PIV3149
Main coil steps number
1
1
4
-
R/W HR1655
PIV3150
Compressor type (FALSE: ON/OFF; TRUE: BLDC)
TRUE
0
1
-
R/W CS291
BV291
Enable EVD emb management
TRUE
0
1
-
R/W CS292
BV292
Da03
Cooling coil PID parameters - Proportional gain
8.0
0.0
999.9
-
R/W HR1656
AV3151
Cooling coil PID parameters - Integral time
120
0
999
-
R/W HR1657
PIV3152
Da06
Heating coil PID parameters - Proportional gain
8.0
0.0
999.9
-
R/W HR1658
AV3153
Heating coil PID parameters - Integral time
120
0
999
-
R/W HR1659
PIV3154
Da09
Dehumidifi cation PID parameters - Proportional gain
8.0
0.0
999.9
-
R/W HR1660
AV3155
Dehumidifi cation PID parameters - Integral time
120
0
999
-
R/W HR1661
PIV3156
Dehumidifi cation PID parameters - Derivative time
0
0
999
-
R/W HR1662
PIV3157
Maximum dehumidifi cation off set
2.0
-99.9
99.9
K
R/W HR1663
AV3158
Da12
Heating coil request during antifreeze off status
50.0
0.0
100.0
%
R/W HR1664
AV3159
Da18
Cooling coil request during antifreeze off status
50.0
0.0
100.0
%
R/W HR1665
AV3160
Da21
Cooling/Heating coil pumps number
0
0
2
-
R/W HR1666
PIV3161
Cooling/Heating coil pumps fl ow check startup delay
15
0
999
s
R/W HR1667
PIV3162
Cooling/Heating coil pumps fl ow check run delay
5
0
999
s
R/W HR1668
PIV3163
Cooling/Heating coil pumps enable antilock function
TRUE
0
1
-
R/W CS293
BV293
Cooling/Heating coil pumps rotation time
24
0
999
h
R/W HR1669
PIV3164
Da24
Coil fl oating valve:Running time
180
1
999
s
R/W HR1914
PIV3940
Db01
PreHeating coil steps number
1
1
4
-
R/W HR1670
PIV3165
Db03
Pre heating PID parameters - Proportional gain
8.0
0.0
999.9
-
R/W HR1671
AV3166
Pre heating PID parameters - Integral time
120
0
999
-
R/W HR1672
PIV3167
Db06
PreHeating coil request during antifreeze off status
50.0
0.0
100.0
%
R/W HR1673
AV3168
Db09
PreHeating coil pumps number
0
0
2
-
R/W HR1674
PIV3169
PreHeating coil pumps fl ow check startup delay
15
0
999
s
R/W HR1675
PIV3170
PreHeating coil pumps fl ow check run delay
5
0
999
s
R/W HR1676
PIV3171
PreHeating coil pumps enable antilock function
TRUE
0
1
-
R/W CS294
BV294
PreHeating coil pumps rotation time
24
0
999
h
R/W HR1677
PIV3172
Db12
Coil fl oating valve:Running time
180
1
999
s
R/W HR1914
PIV3940
Dc01
PostHeating coil steps number
1
1
4
-
R/W HR1678
PIV3173
Dc03
Post heating PID parameters - Proportional gain
8.0
0.0
999.9
-
R/W HR1679
AV3174
Post heating PID parameters - Integral time
120
0
999
-
R/W HR1680
PIV3175
Dc06
PostHeating coil request during antifreeze off status
50.0
0.0
100.0
%
R/W HR1681
AV3176
Dc09
Post Heating coil pumps number
0
0
2
-
R/W HR1682
PIV3177
Re Heating coil pumps fl ow check startup delay
15
0
999
s
R/W HR1683
PIV3178
ReHeating coil pumps fl ow check run delay
5
0
999
s
R/W HR1684
PIV3179
Re Heating coil pumps enable antilock function
TRUE
0
1
-
R/W CS295
BV295
Re Heating coil pumps rotation time
24
0
999
h
R/W HR1685
PIV3180
Dc12
Coil fl oating valve:Running time
180
1
999
s
R/W HR1914
PIV3940
Tab. 9.t
9.10
D
irect expansion with integrated management
9.10.1
C
ompressor management
k.air manages ON/OFF compressors with direct starting or modulating BLDC compressors. For BLDC compressors, more than
200 models can be selected. A BLDC compressor is always driven by a Power+ inverter connected via Modbus (Fieldbus or
Fieldbus2)
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
U
N
IT
Ac08
PreHeating coil type
0
0
5
-
R/W HR1296
PIV2804
Main coil type
0
0
7
-
R/W HR1297
PIV2805
PostHeating coil type
0
0
5
-
R/W HR1298
PIV2806
Tab. 9.u