92
Functions
k.air +030220981 rel. 1.2 - 01.12.2020
Example:
In the event of a fan control probe error and a supply temperature probe error, the fan is activated based on the request set for
a supply temperature probe error.
Note
: in the event of a room probe error, the controller will use the supply temperature probe reading and the last set point
set on the user interface. The room control off set is set to zero.
9.27
O
perating profi les
The controller has four operating profi les, which are selected when setting the time bands: Off (off ), Economy, Precomfort,
Comfort. See chapter “User interface”. For each operating mode, the following can be set: heating and cooling temperature set
point, according to the selected control probe, diff erential pressure/air fl ow-rate set point, air quality set point, room humidity
set point.
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
U
N
IT
Aa03 Unit setpoints - Supply temperature - Cooling - Economy - Setpoint
28.0
LowLimVal
HiLimVal
°C
R/W HR1062
AV2572
Unit setpoints - Supply temperature - Heating - Economy - Setpoint
18.0
LowLimVal
HiLimVal
°C
R/W HR1063
AV2573
Unit setpoints - Supply temperature - Cooling - Economy - Low limit value
18.0
0.0
HiLimVal
°C
R/W HR1064
AV2574
Unit setpoints - Supply temperature - Heating - Economy - Low limit value
16.0
0.0
HiLimVal
°C
R/W HR1065
AV2575
Unit setpoints - Supply temperature - Cooling - Economy - High limit value 30.0
LowLimVal
100.0
°C
R/W HR1066
AV2576
Unit setpoints - Supply temperature - Heating - Economy - High limit value 26.0
LowLimVal
100.0
°C
R/W HR1067
AV2577
Aa06 Unit setpoints - Supply temperature - Cooling - Pre-comfort - Setpoint
26.0
LowLimVal
HiLimVal
°C
R/W HR1068
AV2578
Unit setpoints - Supply temperature - Heating - Pre-comfort - Setpoint
20.0
LowLimVal
HiLimVal
°C
R/W HR1069
AV2579
Unit setpoints - Supply temperature - Cooling - Pre-comfort - Low limit value 16.0
0.0
HiLimVal
°C
R/W HR1070
AV2580
Unit setpoints - Supply temperature - Heating - Pre-comfort - Low limit value 18.0
0.0
HiLimVal
°C
R/W HR1071
AV2581
Unit setpoints - Supply temperature - Cooling - Pre-comfort - High limit value 28.0
LowLimVal
100.0
°C
R/W HR1072
AV2582
Unit setpoints - Supply temperature - Heating - Pre-comfort - High limit value 28.0
LowLimVal
100.0
°C
R/W HR1073
AV2583
Aa09 Scheduler: confi guration - Enabled
FALSE
0
1
-
R
CS064
BV64
Unit setpoints - Supply temperature - Cooling - Comfort - Setpoint
26.0
LowLimVal
HiLimVal
°C
R/W HR1074
AV2584
Unit setpoints - Supply temperature - Heating - Comfort - Setpoint
20.0
LowLimVal
HiLimVal
°C
R/W HR1075
AV2585
Unit setpoints - Supply temperature - Cooling - Comfort - Low limit value 16.0
0.0
HiLimVal
°C
R/W HR1076
AV2586
Unit setpoints - Supply temperature - Heating - Comfort - Low limit value 18.0
0.0
HiLimVal
°C
R/W HR1077
AV2587
Unit setpoints - Supply temperature - Cooling - Comfort - High limit value 28.0
LowLimVal
100.0
°C
R/W HR1078
AV2588
Unit setpoints - Supply temperature - Heating - Comfort - High limit value 28.0
LowLimVal
100.0
°C
R/W HR1079
AV2589
Aa12 Unit setpoints - Return temperature - Cooling - Economy - Setpoint
26.0
LowLimVal
HiLimVal
°C
R/W HR1080
AV2590
Unit setpoints - Return temperature - Heating - Economy - Setpoint
20.0
LowLimVal
HiLimVal
°C
R/W HR1081
AV2591
Unit setpoints - Return temperature - Cooling - Economy - Low limit value
23.0
0.0
HiLimVal
°C
R/W HR1082
AV2592
Unit setpoints - Return temperature - Heating - Economy - Low limit value
18.0
0.0
HiLimVal
°C
R/W HR1083
AV2593
Unit setpoints - Return temperature - Cooling - Economy - High limit value
28.0
LowLimVal
100.0
°C
R/W HR1084
AV2594
Unit setpoints - Return temperature - Heating - Economy - High limit value
23.0
LowLimVal
100.0
°C
R/W HR1085
AV2595
Aa15 Unit setpoints - Return temperature - Cooling - Pre-comfort - Setpoint
26.0
LowLimVal
HiLimVal
°C
R/W HR1086
AV2596
Unit setpoints - Return temperature - Heating - Pre-comfort - Setpoint
20.0
LowLimVal
HiLimVal
°C
R/W HR1087
AV2597
Unit setpoints - Return temperature - Cooling - Pre-comfort - Low limit value
23.0
0.0
HiLimVal
°C
R/W HR1088
AV2598
Unit setpoints - Return temperature - Heating - Pre-comfort - Low limit value
18.0
0.0
HiLimVal
°C
R/W HR1089
AV2599
Unit setpoints - Return temperature - Cooling - Pre-comfort - High limit value 28.0
LowLimVal
100.0
°C
R/W HR1090
AV2600
Unit setpoints - Return temperature - Heating - Pre-comfort - High limit value 23.0
LowLimVal
100.0
°C
R/W HR1091
AV2601
Aa18 Scheduler: confi guration - Enabled
FALSE
0
1
-
R
CS064
BV64
Unit setpoints - Return temperature - Cooling - Comfort - Setpoint
26.0
LowLimVal
HiLimVal
°C
R/W HR1092
AV2602
Unit setpoints - Return temperature - Heating - Comfort - Setpoint
20.0
LowLimVal
HiLimVal
°C
R/W HR1093
AV2603
Unit setpoints - Return temperature - Cooling - Comfort - Low limit value 23.0
0.0
HiLimVal
°C
R/W HR1094
AV2604
Unit setpoints - Return temperature - Heating - Comfort - Low limit value 18.0
0.0
HiLimVal
°C
R/W HR1095
AV2605
Unit setpoints - Return temperature - Cooling - Comfort - High limit value 28.0
LowLimVal
100.0
°C
R/W HR1096
AV2606
Unit setpoints - Return temperature - Heating - Comfort - High limit value 23.0
LowLimVal
100.0
°C
R/W HR1097
AV2607
Aa21 Unit setpoints - Room temperature - Cooling - Economy - Setpoint
26.0
LowLimVal
HiLimVal
°C
R/W HR1098
AV2608
Unit setpoints - Room temperature - Heating - Economy - Setpoint
20.0
LowLimVal
HiLimVal
°C
R/W HR1099
AV2609
Unit setpoints - Room temperature - Cooling - Economy - Low limit value 23.0
0.0
HiLimVal
°C
R/W HR1100
AV2610
Unit setpoints - Room temperature - Heating - Economy - Low limit value 18.0
0.0
HiLimVal
°C
R/W HR1101
AV2611
Unit setpoints - Room temperature - Cooling - Economy - High limit value 28.0
LowLimVal
100.0
°C
R/W HR1102
AV2612
Unit setpoints - Room temperature - Heating - Economy - High limit value
23.0
LowLimVal
100.0
°C
R/W HR1103
AV2613
Aa24 Unit setpoints - Room temperature - Cooling - Pre-comfort - Setpoint
26.0
LowLimVal
HiLimVal
°C
R/W HR1104
AV2614
Unit setpoints - Room temperature - Heating - Pre-comfort - Setpoint
20.0
LowLimVal
HiLimVal
°C
R/W HR1105
AV2615
Unit setpoints - Room temperature - Cooling - Pre-comfort - Low limit value 23.0
0.0
HiLimVal
°C
R/W HR1106
AV2616
Unit setpoints - Room temperature - Heating - Pre-comfort - Low limit value
18.0
0.0
HiLimVal
°C
R/W HR1107
AV2617
Unit setpoints - Room temperature - Cooling - Pre-comfort - High limit value
28.0
LowLimVal
100.0
°C
R/W HR1108
AV2618
Unit setpoints - Room temperature - Heating - Pre-comfort - High limit value
23.0
LowLimVal
100.0
°C
R/W HR1109
AV2619