45
Commissioning
k.air +030220981 rel. 1.2 - 01.12.2020
8.5 Input/output
confi guration
k.air features free input/output mapping. For each device, sensor or contact (referred to as “points”), an acquisition channel needs
to be selected from those available on the main board or expansions.
Menu W.In/Out is used to confi gure and check the inputs and outputs connected to the k.air controller.
IO Conf. AIN Wb01
SUPPLY TEMPERATURE
Probe:
Minimum:
Maximim
Board:MB
Offset:
Value:
4..20mA
-30.0°C
70.0°C
Ch: U1
0.0°C Filt:5
29.1°C
30220980_127_R01
There are four confi guration screens:
• Wb01 - AIN (analogue inputs)
• Wb02 - DIN (digital inputs)
• Wb03 - DOUT (digital outputs)
• Wb04 - AOUT (analogue outputs).
Each of these shows a scrollable list of all the inputs/outputs available, fi ltered based on the unit confi guration, so as to assign
the reference channel and set the other fundamental parameters for processing the signal.
The following acquisition channels are available:
I
D
Type
D
escription
1
MB
Main board
2
E1
Expansion 1
3
E2
Expansion 2
4
E3
Expansion 3
5
E4
Expansion 4
6
SERIAL
Serial probes (max 10) and pGDx
7
KWATER
Probes connected to k.water
Tab. 8.o
Note:
the channels already associated with a point cannot be reused; k.air fi lters the channels and only proposes those that
are free, depending on the type of HW selected.
Note:
universal channels (“U”) are available as AIN, DIN and AOUT.
The following parameters are available for each point:
G
roup
P
arameter
D
escription
AIN
Probe type
0:--; 1:NTC; 2:NTC-HT; 3: NTC-80; 4:PT1000; 6: 0..1V; 7: 0..10V; 8:0..5Vdc
c.pco; 9:0..5Vdc ext; 10:0,5..4,5V; 11: 4..20mA; 12:0..20mA; 13: COUNTER; 14:FREQUENCY;
Minimum
Minimum conversion range for active probes
Maximum
Maximum conversion range for active probes
Off set
Probe calibration
Filter
Sensor fi lter (0: no fi lter ... 9: high fi ltering)
DIN
Logic
NC / NO contact logic
DOUT
Logic
NO / NC contact logic
AOUT
Minimum
Minimum output signal conversion value
Maximum
Maximum output signal conversion value
Tab. 8.p
Note:
the minimum and maximum conversion values rescale the output signal. Specifi cally, the minimum value is also active
when the unit is OFF.
8.6 Unit of measure
The k.Air controller is confi gured to display International System units of measure. Access screen Wc01 to set a diff erent unit of
measure, if desired. The options are international system (Int), Imperial (UK) and other systems used in the United States (USA)
and Canada (CAN). Below is a table showing the units of measure for each physical measurement, according to the selected
system.
R
ef.
D
isplay description
Xc01
Unit of measure setting bar/°C/Pa/m3h ¦ KPa/°C/Pa/m3h ¦ psi/°F/”wc/cfm ¦ psi/°C/”wc/cfm ¦
S
election
R
efrigerant circuit pressure
Temper.
S
tatic pressure
F
low-rate
CO
2
Humidity
bar/°C/Pa/m 3 h
bars
°C
Pa
m3/h
ppm
% H.R.
KPa/°C/Pa/m 3 h
KPa
°C
Pa
m3/h
ppm
% H.R.
psi/°F/”wc/cfm
psi
°F
“wc
cfm
ppm
% H.R.
psi/°C/”wc/cfm
psi
°C
“wc
cfm
ppm
% H.R.
Tab. 8.q