106
Parameter table
k.air +030220981 rel. 1.2 - 01.12.2020
10. PARAMETER TABLE
The k.Air controller can be programmed in three levels, with access to diff erent parameters based on the password entered (see
the parameter table):
1. U = user (password=0000);
2. S = service (password=1234);
3. M = manufacturer (password=5678).
The k.Air parameters can be reset to the default values using the command available on screen Ac34.
R
ef.
D
escription
D
ef.
U
O
M
Min
Max
Ac34
Reset parameters to default values
No
-
No
Yes
Tab. 10.a
Important:
the operation to reset the default values is not reversible, unless a user confi guration has been previously saved;
see the paragraph on commissioning.
10.1
P
arameter table
10.1.1
A
. Unit
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
U
N
IT
Aa03
Unit setpoints - Supply temperature - Cooling - Economy - Setpoint
28.0
LowLimVal
HiLimVal
°C
R/W HR1062
AV2572
Unit setpoints - Supply temperature - Heating - Economy - Setpoint
18.0
LowLimVal
HiLimVal
°C
R/W HR1063
AV2573
Unit setpoints - Supply temperature - Cooling - Economy - Low limit value
18.0
0.0
HiLimVal
°C
R/W HR1064
AV2574
Unit setpoints - Supply temperature - Heating - Economy - Low limit value
16.0
0.0
HiLimVal
°C
R/W HR1065
AV2575
Unit setpoints - Supply temperature - Cooling - Economy - High limit value 30.0
LowLimVal
100.0
°C
R/W HR1066
AV2576
Unit setpoints - Supply temperature - Heating - Economy - High limit value 26.0
LowLimVal
100.0
°C
R/W HR1067
AV2577
Aa06
Unit setpoints - Supply temperature - Cooling - Pre-comfort - Setpoint 26.0
LowLimVal
HiLimVal
°C
R/W HR1068
AV2578
Unit setpoints - Supply temperature - Heating - Pre-comfort - Setpoint 20.0
LowLimVal
HiLimVal
°C
R/W HR1069
AV2579
Unit setpoints - Supply temperature - Cooling - Pre-comfort -
Low limit value
16.0
0.0
HiLimVal
°C
R/W HR1070
AV2580
Unit setpoints - Supply temperature - Heating - Pre-comfort -
Low limit value
18.0
0.0
HiLimVal
°C
R/W HR1071
AV2581
Unit setpoints - Supply temperature - Cooling - Pre-comfort -
High limit value
28.0
LowLimVal
100.0
°C
R/W HR1072
AV2582
Unit setpoints - Supply temperature - Heating - Pre-comfort -
High limit value
28.0
LowLimVal
100.0
°C
R/W HR1073
AV2583
Aa09
Scheduler: confi guration - Enabled
FALSE
0
1
-
R
CS064
BV64
Unit setpoints - Supply temperature - Cooling - Comfort - Setpoint
26.0
LowLimVal
HiLimVal
°C
R/W HR1074
AV2584
Unit setpoints - Supply temperature - Heating - Comfort - Setpoint
20.0
LowLimVal
HiLimVal
°C
R/W HR1075
AV2585
Unit setpoints - Supply temperature - Cooling - Comfort - Low limit value
16.0
0.0
HiLimVal
°C
R/W HR1076
AV2586
Unit setpoints - Supply temperature - Heating - Comfort - Low limit value
18.0
0.0
HiLimVal
°C
R/W HR1077
AV2587
Unit setpoints - Supply temperature - Cooling - Comfort - High limit value
28.0
LowLimVal
100.0
°C
R/W HR1078
AV2588
Unit setpoints - Supply temperature - Heating - Comfort - High limit value
28.0
LowLimVal
100.0
°C
R/W HR1079
AV2589
Aa12
Unit setpoints - Return temperature - Cooling - Economy - Setpoint
26.0
LowLimVal
HiLimVal
°C
R/W HR1080
AV2590
Unit setpoints - Return temperature - Heating - Economy - Setpoint
20.0
LowLimVal
HiLimVal
°C
R/W HR1081
AV2591
Unit setpoints - Return temperature - Cooling - Economy - Low limit value
23.0
0.0
HiLimVal
°C
R/W HR1082
AV2592
Unit setpoints - Return temperature - Heating - Economy - Low limit value
18.0
0.0
HiLimVal
°C
R/W HR1083
AV2593
Unit setpoints - Return temperature - Cooling - Economy - High limit value
28.0
LowLimVal
100.0
°C
R/W HR1084
AV2594
Unit setpoints - Return temperature - Heating - Economy - High limit value 23.0
LowLimVal
100.0
°C
R/W HR1085
AV2595
Aa15
Unit setpoints - Return temperature - Cooling - Pre-comfort - Setpoint 26.0
LowLimVal
HiLimVal
°C
R/W HR1086
AV2596
Unit setpoints - Return temperature - Heating - Pre-comfort - Setpoint 20.0
LowLimVal
HiLimVal
°C
R/W HR1087
AV2597
Unit setpoints - Return temperature - Cooling - Pre-comfort -
Low limit value
23.0
0.0
HiLimVal
°C
R/W HR1088
AV2598
Unit setpoints - Return temperature - Heating - Pre-comfort -
Low limit value
18.0
0.0
HiLimVal
°C
R/W HR1089
AV2599
Unit setpoints - Return temperature - Cooling - Pre-comfort -
High limit value
28.0
LowLimVal
100.0
°C
R/W HR1090
AV2600
Unit setpoints - Return temperature - Heating - Pre-comfort -
High limit value
23.0
LowLimVal
100.0
°C
R/W HR1091
AV2601
Aa18
Scheduler: confi guration - Enabled
FALSE
0
1
-
R
CS064
BV64
Unit setpoints - Return temperature - Cooling - Comfort - Setpoint
26.0
LowLimVal
HiLimVal
°C
R/W HR1092
AV2602
Unit setpoints - Return temperature - Heating - Comfort - Setpoint
20.0
LowLimVal
HiLimVal
°C
R/W HR1093
AV2603
Unit setpoints - Return temperature - Cooling - Comfort - Low limit value
23.0
0.0
HiLimVal
°C
R/W HR1094
AV2604
Unit setpoints - Return temperature - Heating - Comfort - Low limit value
18.0
0.0
HiLimVal
°C
R/W HR1095
AV2605
Aa18
Unit setpoints - Return temperature - Cooling - Comfort - High limit value
28.0
LowLimVal
100.0
°C
R/W HR1096
AV2606
Unit setpoints - Return temperature - Heating - Comfort - High limit value
23.0
LowLimVal
100.0
°C
R/W HR1097