Supervisor variable table
k.air +030220981 rel. 1.2 - 01.12.2020
Variable
D
escription
D
im Modbus
BAC
net
SuctT.Enable_W
Suction temperature - Enable input
1
DI087
BV545
SuctT.Confi gured_R
Suction temperature - Analog input confi gured
1
DI088
BV546
SuctT.PrbOk_R
Suction temperature - Probe working correctly
1
DI089
BV547
SuctT.Alrm_R
Suction temperature - Alarm probe broken or disconnected
1
DI090
BV548
FreshAirPreHeatWaterTemp.Enable_W
Fresh Air Pre-Heat coil water temperature - Enable input
1
DI091
BV549
FreshAirPreHeatWaterTemp.Confi gured_R
Fresh Air Pre-Heat coil water temperature -
Analog input confi gured
1
DI092
BV550
FreshAirPreHeatWaterTemp.PrbOk_R
Fresh Air Pre-Heat coil water temperature -
Probe working correctly
1
DI093
BV551
FreshAirPreHeatWaterTemp.Alrm_R
Fresh Air Pre-Heat coil water temperature -
Alarm probe broken or disconnected
1
DI094
BV552
PreHeatCoilWaterTemp.Enable_W
Preheat coil water temperature - Enable input
1
DI095
BV553
PreHeatCoilWaterTemp.Confi gured_R
Preheat coil water temperature - Analog input confi gured
1
DI096
BV554
PreHeatCoilWaterTemp.PrbOk_R
Preheat coil water temperature - Probe working correctly
1
DI097
BV555
PreHeatCoilWaterTemp.Alrm_R
Preheat coil water temperature - Alarm probe broken
or disconnected
1
DI098
BV556
MainCoilWaterTemp.Enable_W
Main coil water temperature - Enable input
1
DI099
BV557
MainCoilWaterTemp.Confi gured_R
Main coil water temperature - Analog input confi gured
1
DI100
BV558
Al_NOT_USED.Active
Alarm to make the alarms list compatible with mask -
Alarm status
1
DI1000
BV1229
Al_SupplyTemp.Active
Supply temperature probe alarm - Alarm status
1
DI1001
BV1230
Al_SupplyHum.Active
Supply humidity probe alarm - Alarm status
1
DI1002
BV1231
Al_RetTemp.Active
Return temperature probe alarm - Alarm status
1
DI1003
BV1232
Al_RetHum.Active
Return humidity probe alarm - Alarm status
1
DI1004
BV1233
Al_RoomTemp.Active
Room temperature probe alarm - Alarm status
1
DI1005
BV1234
Al_RoomHum.Active
Room humidity probe alarm - Alarm status
1
DI1006
BV1235
Al_ExtTemp.Active
Fresh air temperature probe alarm - Alarm status
1
DI1007
BV1236
Al_ExtHum.Active
Fresh air humidity probe alarm - Alarm status
1
DI1008
BV1237
Al_ExhTemp.Active
Exhaust temperature probe alarm - Alarm status
1
DI1009
BV1238
MainCoilWaterTemp.PrbOk_R
Main coil water temperature - Probe working correctly
1
DI101
BV559
Al_ExhHum.Active
Exhaust humidity probe alarm - Alarm status
1
DI1010
BV1239
Al_AFreezeTemp.Active
Antifreeze temperature probe alarm - Alarm status
1
DI1011
BV1240
Al_SatTemp.Active
Saturation temperature probe alarm - Alarm status
1
DI1012
BV1241
Al_SatHum.Active
Saturation humidity probe alarm - Alarm status
1
DI1013
BV1242
Al_FreshAirPreHeatTemp.Active
Fresh Air Pre-Heattemperature probe alarm - Alarm status
1
DI1014
BV1243
Al_SupplyAirP.Active
Supply air pressure probe alarm - Alarm status
1
DI1015
BV1244
Al_RetAirP.Active
Return air pressure probe alarm - Alarm status
1
DI1016
BV1245
Al_AirQuality_CO2.Active
CO2 sensor probe alarm - Alarm status
1
DI1017
BV1246
Al_AirQuality_VOC.Active
VOC sensor probe alarm - Alarm status
1
DI1018
BV1247
Al_DscgP.Active
Discharge pressure probe alarm - Alarm status
1
DI1019
BV1248
MainCoilWaterTemp.Alrm_R
Main coil water temperature - Alarm probe broken
or disconnected
1
DI102
BV560
Al_DscgT.Active
Discharge temperature probe alarm - Alarm status
1
DI1020
BV1249
Al_SuctP.Active
Suction pressure probe alarm - Alarm status
1
DI1021
BV1250
Al_SuctT.Active
Suction temperature probe alarm - Alarm status
1
DI1022
BV1251
Al_FreshAirPreHeatWaterTemp.Active
Fresh Air Pre-Heat coil water temperature probe alarm -
Alarm status
1
DI1023
BV1252
Al_PreHeatCoilWaterTemp.Active
Preheat coil water temperature probe alarm - Alarm status
1
DI1024
BV1253
Al_MainCoilWaterTemp.Active
Main coil water temperature probe alarm - Alarm status
1
DI1025
BV1254
Al_ReHeatCoilWaterTemp.Active
Re heat coil water temperature probe alarm - Alarm status
1
DI1026
BV1255
Al_AuxPrb_1.Active
Auxiliary probe 1 probe alarm - Alarm status
1
DI1027
BV1256
Al_AuxPrb_2.Active
Auxiliary probe 2 probe alarm - Alarm status
1
DI1028
BV1257
Al_AuxPrb_3.Active
Auxiliary probe 3 probe alarm - Alarm status
1
DI1029
BV1258
ReHeatCoilWaterTemp.Enable_W
Postheat coil water temperature - Enable input
1
DI103
BV561
Al_AuxPrb_4.Active
Auxiliary probe 4 probe alarm - Alarm status
1
DI1030
BV1259
Al_Ain_SetP.Active
Setpoint by AIN probe alarm - Alarm status
1
DI1031
BV1260
Al_SupplyRecoveryTemp.Active
Supply recovery temperature probe alarm - Alarm status
1
DI1032
BV1261
Al_RetRecoveryTemp.Active
Return recovery temperature probe alarm - Alarm status
1
DI1033
BV1262
Al_HepaFilt_1.Active
Hepa fi lter 1 probe alarm - Alarm status
1
DI1034
BV1263
Al_HepaFilt_2.Active
Hepa fi lter 2 probe alarm - Alarm status
1
DI1035
BV1264
Al_GenericAlrmByDin.Active
Generic alarm from digital input - Alarm status
1
DI1036
BV1265
Al_MainHeat_Ovld.Active
Main heater alarm - Alarm status
1
DI1037
BV1266
Al_SupplyFanOvld.Active
Supply fan overload - Alarm status
1
DI1038
BV1267
Al_RetFanOvld.Active
Return fan overload - Alarm status
1
DI1039
BV1268
ReHeatCoilWaterTemp.Confi gured_R
Postheat coil water temperature - Analog input confi gured
1
DI104
BV562