111
Parameter table
k.air +030220981 rel. 1.2 - 01.12.2020
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
U
N
IT
Ac12
Fresh air damper type (0: On/Off ; 1: Modulating)
0
0
2
-
R/W HR1299
PIV2807
Exhaust air damper type (0: On/Off ; 1: Modulating)
0
0
2
-
R/W HR1300
PIV2808
Mixing air damper type (0: On/Off ; 1: Modulating)
0
0
2
-
R/W HR1301
PIV2809
Supply air damper type (0: On/Off ; 1: Modulating)
0
0
2
-
R/W HR1302
PIV2810
Return air damper type (0: On/Off ; 1: Modulating)
0
0
2
-
R/W HR1303
PIV2811
Bypass damper type (0: On/Off ; 1: Modulating)
0
0
1
-
R/W HR1304
PIV2812
Ac16
Filters confi guration
0
0
6
-
R/W HR1305
PIV2813
HEPA Filter confi guration (0: None; 1: Filt 1; Filt 1 & 2)
0
0
2
-
R/W HR1306
PIV2814
Ac18
Regulation type (0: Supply only; 1:Return only; 2: Room only; 3: Return
+ Supply; 4: Room + Supply; 5: Disabled)
5
0
5
-
R/W HR1307
PIV2815
Ac20
Regulation set point off set: proportional gain
5.0
0.0
999.9
-
R/W HR1308
AV2816
Regulation set point off set: integral time
150
0
999
s
R/W HR1309
PIV2817
Ac22
Machine type (0: COOLING; 1: HEATING; 2: COOL/HEAT)
2
0
2
-
R/W HR1310
PIV2818
Machine type cooling/heating enabled
-
0
1
-
R
DI700
BV1158
Unit cooling heating mode confi guration
0
0
6
-
R/W HR1311
PIV2819
Ac24
Cooling external temperature threshold
28.0
-99.9
99.9
°C
R/W HR1312
AV2820
Heating external temperature threshold
18.0
-99.9
99.9
°C
R/W HR1313
AV2821
Ac28
Cooling/Heating coil water temperature cooling threshold
15.0
-99.9
99.9
°C
R/W HR1314
AV2822
Cooling/Heating coil water temperature heating threshold
25.0
-99.9
99.9
°C
R/W HR1315
AV2823
Ac30
Main coil: water temperature out of range warning delay time
5
1
999
min
R/W HR1316
PIV2824
Coil water temperature: action confi guration
0
0
2
-
R/W HR1317
PIV2825
Ac32
Humidifi cation/Dehumidifi cation: Control probe
0
0
2
-
R/W HR1318
PIV2826
Humidifi cation/Dehumidifi cation: Control type
0
0
1
-
R/W HR1319
PIV2827
Ac34
Dehumidifi cation: Regulation type
0
0
1
-
R/W HR1320
PIV2828
Dehumidifi cation: enable kwater dew point calculation
FALSE
0
1
-
R/W CS227
BV227
Ac36
Humidifi cation/Dehumidifi cation: Regulation band
20.0
1.0
99.0
%rh
R/W HR1321
AV2829
Humidifi cation/Dehumidifi cation: Regulation change delay time
5
0
99
min
R/W HR1322
PIV2830
Ac11
Freecooling activation delta
3.0
0.0
20.0
K
R/W HR1323
AV2831
Freeheating activation delta
3.0
0.0
20.0
K
R/W HR1324
AV2832
Ac40
Free cooling PID parameters - Proportional gain
8.0
0.0
999.9
-
R/W HR1325
AV2833
Free cooling PID parameters - Integral time
120
0
999
-
R/W HR1326
PIV2834
Ac42
Free heating PID parameters - Proportional gain
8.0
0.0
999.9
-
R/W HR1327
AV2835
Free heating PID parameters - Integral time
120
0
999
-
R/W HR1328
PIV2836
Ac44
Enable warm up procedure during start up state
FALSE
0
1
-
R/W CS228
BV228
Low external temperature threshold for the activation of warm up
procedure
-1.0
-99.0
99.0
°C
R/W HR1329
AV2837
Settable delay between return and supply fan activation (seconds).
To be used only when warm up procedure is disabled
15
1
999
s
R/W HR1330
PIV2838
Warm up delay time
15
1
60
s
R/W HR1331
PIV2839
Warm up fan activation delay time
15
0
600
s
R/W HR1332
PIV2840
Ac46
For mask usage
1
0
3
-
R/W HR1333
PIV2841
Supply fan request for automatic warm up
30.0
0.0
100.0
%
R/W HR1334
AV2842
For mask usage
0
0
100
-
R/W HR1335
PIV2843
Enable return fan
FALSE
0
1
-
R
CS225
BV225
For mask usage
0
0
3
-
R/W HR1336
PIV2844
Return fan request for automatic warm up
30.0
0.0
100.0
%
R/W HR1337
AV2845
For mask usage
0
0
100
-
R/W HR1338
PIV2846
Ac48
PreHeating coil warm up request
0.0
0.0
100.0
-
R/W HR1339
AV2847
Main coil warm up request
0.0
0.0
100.0
-
R/W HR1340
AV2848
PostHeating coil warm up request
0.0
0.0
100.0
-
R/W HR1341
AV2849
Bypass damper warm up request
0.0
0.0
100.0
-
R/W HR1342
AV2850
Thermal wheel warm up request
0.0
0.0
100.0
%
R/W HR1343
AV2851
For mask usage
0
0
100
-
R/W HR1344
PIV2852
Ac50
For mask usage
2
0
3
-
R/W HR1345
PIV2853
Supply fan request for automatic switch on when warm up
is not enabled
25.0
0.0
100.0
%
R/W HR1346
AV2854
For mask usage
100
0
100
-
R/W HR1347
PIV2855
Ac52
Antifreeze type (0: NONE; 1: Ext.Temp.; 2: AFreeze Temp.;
3: DigitalInput)
0
0
3
-
R/W HR1348
PIV2856
Ac54
Antifreeze temperature threshold
2.0
-50.0
20.0
°C
R/W HR1349
AV2857
Antifreeze ending delta
3.0
0.0
15.0
K
R/W HR1350
AV2858
Ac56
Anti freeze warning delay time
30
0
999
s
R/W HR1351
PIV2859
Antifreeze alarm delay time
5
0
999
s
R/W HR1352
PIV2860
Enable antifreeze during off state
FALSE
0
1
-
R/W CS229
BV229
Ac58
Prevent antifreeze threshold
5.0
-99.9
99.9
°C
R/W HR1353
AV2861
Ac60
Low supply temperature threshold
16.0
0.0
25.0
°C
R/W HR1354
AV2862
Low supply temperature alarm delay time at start up
999
0
65535
s
R/W HR1355
PIV2863
Low supply temperature alarm delay time at unit in run mode
600
0
65535
s
R/W HR1356
PIV2864