93
Functions
k.air +030220981 rel. 1.2 - 01.12.2020
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
U
N
IT
Aa27 Scheduler: confi guration - Enabled
FALSE
0
1
-
R
CS064
BV64
Unit setpoints - Room temperature - Cooling - Comfort - Setpoint
26.0
LowLimVal
HiLimVal
°C
R/W HR1110
AV2620
Unit setpoints - Room temperature - Heating - Comfort - Setpoint
20.0
LowLimVal
HiLimVal
°C
R/W HR1111
AV2621
Unit setpoints - Room temperature - Cooling - Comfort - Low limit value 23.0
0.0
HiLimVal
°C
R/W HR1112
AV2622
Unit setpoints - Room temperature - Heating - Comfort - Low limit value
18.0
0.0
HiLimVal
°C
R/W HR1113
AV2623
Unit setpoints - Room temperature - Cooling - Comfort - High limit value
28.0
LowLimVal
100.0
°C
R/W HR1114
AV2624
Unit setpoints - Room temperature - Heating - Comfort - High limit value 23.0
LowLimVal
100.0
°C
R/W HR1115
AV2625
Aa30 Unit setpoints - Supply static pressure - Economy - Setpoint
400.0
LowLimVal
HiLimVal
Pa
R/W HR1116
AV2626
Unit setpoints - Supply static pressure - Economy - Setpoint
400.0
LowLimVal
HiLimVal
Pa
R/W HR1116
AV2626
Unit setpoints - Supply static pressure - Economy - Low limit value
200.0
MinVal_RW HiLimVal
Pa
R/W HR1117
AV2627
Unit setpoints - Supply static pressure - Economy - Low limit value
200.0
MinVal_RW HiLimVal
Pa
R/W HR1117
AV2627
Unit setpoints - Supply static pressure - Economy - High limit value
600.0
LowLimVal
MaxVal_ RW Pa
R/W HR1118
AV2628
Unit setpoints - Supply static pressure - Economy - High limit value
600.0
LowLimVal
MaxVal_ RW Pa
R/W HR1118
AV2628
Aa33 Unit setpoints - Supply static pressure - Pre-comfort - Setpoint
400.0
LowLimVal
HiLimVal
Pa
R/W HR1119
AV2629
Unit setpoints - Supply static pressure - Pre-comfort - Setpoint
400.0
LowLimVal
HiLimVal
Pa
R/W HR1119
AV2629
Unit setpoints - Supply static pressure - Pre-comfort - Low limit value
200.0
MinVal_RW HiLimVal
Pa
R/W HR1120
AV2630
Unit setpoints - Supply static pressure - Pre-comfort - Low limit value
200.0
MinVal_RW HiLimVal
Pa
R/W HR1120
AV2630
Unit setpoints - Supply static pressure - Pre-comfort - High limit value
600.0
LowLimVal
MaxVal_ RW Pa
R/W HR1121
AV2631
Unit setpoints - Supply static pressure - Pre-comfort - High limit value
600.0
LowLimVal
MaxVal_ RW Pa
R/W HR1121
AV2631
Aa36 Scheduler: confi guration - Enabled
FALSE
0
1
-
R
CS064
BV64
Unit setpoints - Supply static pressure - Comfort - Setpoint
400.0
LowLimVal
HiLimVal
Pa
R/W HR1122
AV2632
Unit setpoints - Supply static pressure - Comfort - Setpoint
400.0
LowLimVal
HiLimVal
Pa
R/W HR1122
AV2632
Unit setpoints - Supply static pressure - Comfort - Low limit value
200.0
MinVal_RW HiLimVal
Pa
R/W HR1123
AV2633
Unit setpoints - Supply static pressure - Comfort - Low limit value
200.0
MinVal_RW HiLimVal
Pa
R/W HR1123
AV2633
Aa36 Unit setpoints - Supply static pressure - Comfort - High limit value
600.0
LowLimVal
MaxVal_ RW Pa
R/W HR1124
AV2634
Unit setpoints - Supply static pressure - Comfort - High limit value
600.0
LowLimVal
MaxVal_ RW Pa
R/W HR1124
AV2634
Aa39 Unit setpoints - Supply air fl ow - Setpoint
5000
LowLimVal
HiLimVal
m^3/h
R/W HR1125
PIV2635
Unit setpoints - Supply air fl ow - Low limit value
3000
0
HiLimVal
m^3/h
R/W HR1126
PIV2636
Unit setpoints - Supply air fl ow - High limit value
7000
LowLimVal
65535
m^3/h
R/W HR1127
PIV2637
Aa42 Unit setpoints - Supply air fl ow - Setpoint
5000
LowLimVal
HiLimVal
m^3/h
R/W HR1128
PIV2638
Unit setpoints - Supply air fl ow - Low limit value
3000
0
HiLimVal
m^3/h
R/W HR1129
PIV2639
Unit setpoints - Supply air fl ow - High limit value
7000
LowLimVal
65535
m^3/h
R/W HR1130
PIV2640
Aa45 Scheduler: confi guration - Enabled
FALSE
0
1
-
R
CS064
BV64
Unit setpoints - Supply air fl ow - Setpoint
5000
LowLimVal
HiLimVal
m^3/h
R/W HR1131
PIV2641
Unit setpoints - Supply air fl ow - Low limit value
3000
0
HiLimVal
m^3/h
R/W HR1132
PIV2642
Unit setpoints - Supply air fl ow - High limit value
7000
LowLimVal
65535
m^3/h
R/W HR1133
PIV2643
Aa48 Unit setpoints - Air quality - Economy - Setpoint
800.0
LowLimVal
HiLimVal
ppm
R/W HR1134
AV2644
Unit setpoints - Air quality - Economy - Low limit value
600.0
AirQuality_
MinVal_RW
HiLimVal
ppm
R/W HR1135
AV2645
Unit setpoints - Air quality - Economy - High limit value
1000.0 LowLimVal
MaxVal_ RW ppm
R/W HR1136
AV2646
Aa51 Unit setpoints - Air quality - Pre- comfort - Setpoint
800.0
LowLimVal
HiLimVal
ppm
R/W HR1137
AV2647
Unit setpoints - Air quality - Pre- comfort - Low limit value
600.0
AirQuality_
MinVal_RW
HiLimVal
ppm
R/W HR1138
AV2648
Unit setpoints - Air quality - Pre- comfort - High limit value
1000.0 LowLimVal
MaxVal_ RW ppm
R/W HR1139
AV2649
Aa54 Scheduler: confi guration - Enabled
FALSE
0
1
-
R
CS064
BV64
Unit setpoints - Air quality - Comfort - Setpoint
800.0
LowLimVal
HiLimVal
ppm
R/W HR1140
AV2650
Unit setpoints - Air quality - Comfort - Low limit value
600.0
MinVal_RW HiLimVal
ppm
R/W HR1141
AV2651
Unit setpoints - Air quality - Comfort - High limit value
1000.0 LowLimVal
MaxVal_ RW ppm
R/W HR1142
AV2652
Aa57 Unit setpoints - Return static pressure - Economy - Setpoint
400.0
LowLimVal
HiLimVal
Pa
R/W HR1143
AV2653
Unit setpoints - Return static pressure - Economy - Setpoint
400.0
LowLimVal
HiLimVal
Pa
R/W HR1143
AV2653
Unit setpoints - Return static pressure - Economy - Low limit value
200.0
MinVal_RW HiLimVal
Pa
R/W HR1144
AV2654
Unit setpoints - Return static pressure - Economy - Low limit value
200.0
MinVal_RW HiLimVal
Pa
R/W HR1144
AV2654
Unit setpoints - Return static pressure - Economy - High limit value
600.0
LowLimVal
MaxVal_ RW Pa
R/W HR1145
AV2655
Unit setpoints - Return static pressure - Economy - High limit value
600.0
LowLimVal
MaxVal_ RW Pa
R/W HR1145
AV2655
Aa60 Unit setpoints - Return static pressure - Pre-comfort - Setpoint
400.0
LowLimVal
HiLimVal
Pa
R/W HR1146
AV2656
Unit setpoints - Return static pressure - Pre-comfort - Setpoint
400.0
LowLimVal
HiLimVal
Pa
R/W HR1146
AV2656
Unit setpoints - Return static pressure - Pre-comfort - Low limit value
200.0
MinVal_RW HiLimVal
Pa
R/W HR1147
AV2657
Unit setpoints - Return static pressure - Pre-comfort - Low limit value
200.0
MinVal_RW HiLimVal
Pa
R/W HR1147
AV2657
Unit setpoints - Return static pressure - Pre-comfort - High limit value
600.0
LowLimVal
MaxVal_ RW Pa
R/W HR1148
AV2658
Unit setpoints - Return static pressure - Pre-comfort - High limit value
600.0
LowLimVal
MaxVal_ RW Pa
R/W HR1148
AV2658
Aa63 Scheduler: confi guration - Enabled
FALSE
0
1
-
R
CS064
BV64
Unit setpoints - Return static pressure - Comfort - Setpoint
400.0
LowLimVal
HiLimVal
Pa
R/W HR1149
AV2659
Unit setpoints - Return static pressure - Comfort - Setpoint
400.0
LowLimVal
HiLimVal
Pa
R/W HR1149
AV2659
Unit setpoints - Return static pressure - Comfort - Low limit value
200.0
MinVal_RW HiLimVal
Pa
R/W HR1150
AV2660
Unit setpoints - Return static pressure - Comfort - Low limit value
200.0
MinVal_RW HiLimVal
Pa
R/W HR1150
AV2660
Unit setpoints - Return static pressure - Comfort - High limit value
600.0
LowLimVal
MaxVal_ RW Pa
R/W HR1151
AV2661
Unit setpoints - Return static pressure - Comfort - High limit value
600.0
LowLimVal
MaxVal_ RW Pa
R/W HR1151
AV2661