142
Supervisor variable table
k.air +030220981 rel. 1.2 - 01.12.2020
Variable
D
escription
D
im Modbus
BAC
net
Al_FansOvld.Active
Fans overload - Alarm status
1
DI1040
BV1269
Al_CompOvld.Active
Compressor overload - Alarm status
1
DI1041
BV1270
Al_HiP_Sw.Active
High discharge pressure switch - Alarm status
1
DI1042
BV1271
Al_LowP_Sw.Active
Low suction pressure switch - Alarm status
1
DI1043
BV1272
Al_SupplyAirFlwSw.Active
Supply air fl ow switch alarm - Alarm status
1
DI1044
BV1273
Al_RetAirFlwSw.Active
Return air fl ow switch alarm - Alarm status
1
DI1045
BV1274
Al_AirFlwSw.Active
Air fl ow switch alarm - Alarm status
1
DI1046
BV1275
Al_AFreeze.Active
Antifreeze alarm - Alarm status
1
DI1047
BV1276
Al_LowSH_EVD_Emb.Active
EVD-Low SH - Alarm status
1
DI1048
BV1277
Al_EEV_MotErr.Active
EVD-Motor error - Alarm status
1
DI1049
BV1278
ReHeatCoilWaterTemp.PrbOk_R
Postheat coil water temperature - Probe working correctly
1
DI105
BV563
Al_SettingOutOfBound_EVD_Emb.Active
EVD-Setting out of bound - Alarm status
1
DI1050
BV1279
Al_RangeErr_EVD_Emb.Active
EVD-Settings range error - Alarm status
1
DI1051
BV1280
Al_InvOffl
ine.Active
Inverter-Offl
ine - Alarm status
1
DI1052
BV1281
Al_Inv01_OverA.Active
Inverter-Drive overcurrent (01) - Alarm status
1
DI1053
BV1282
Al_Inv02_MotOvld.Active
Inverter-Motor overload (02) - Alarm status
1
DI1054
BV1283
Al_Inv03_DC_BusOverV.Active
Inverter-DC Bus overvoltage (03) - Alarm status
1
DI1055
BV1284
Al_Inv04_DC_BusUnderV.Active
Inverter-DC bus undervoltage (04) - Alarm status
1
DI1056
BV1285
Al_Inv05_OverTemp.Active
Inverter-Drive overtemperature (05) - Alarm status
1
DI1057
BV1286
Al_Inv06_DrvUnderTemp.Active
Inverter-Drive undertemperature (06) - Alarm status
1
DI1058
BV1287
Al_Inv07_HW_OverA.Active
Inverter-HW overcurrent HW(07) - Alarm status
1
DI1059
BV1288
ReHeatCoilWaterTemp.Alrm_R
Postheat coil water temperature - Alarm probe broken
or disconnected
1
DI106
BV564
Al_Inv08_MotOverTemp.Active
Inverter-PTC motor overtemperature (08) - Alarm status
1
DI1060
BV1289
Al_Inv09_OutputFault.Active
Inverter-IGBT module error (09) - Alarm status
1
DI1061
BV1290
Al_Inv10_FlashDataErr.Active
Inverter-CPU error (10) - Alarm status
1
DI1062
BV1291
Al_Inv11_ParamDef.Active
Inverter-Parameter default (11) - Alarm status
1
DI1063
BV1292
Al_Inv12_DC_RippTooLarge.Active
Inverter-DC bus ripple (12) - Alarm status
1
DI1064
BV1293
Al_Inv13_MB_CommFault.Active
Inverter-Data communication fault (13) - Alarm status
1
DI1065
BV1294
Al_Inv14_DrvThermistorFault.Active
Inverter-Drive thermistor fault (14) - Alarm status
1
DI1066
BV1295
Al_Inv15_AutotuneFault.Active
Inverter-Autotuning fault (15) - Alarm status
1
DI1067
BV1296
Al_Inv16_DrvDis.Active
Inverter-Drive disabled (16) - Alarm status
1
DI1068
BV1297
Al_Inv17_MotPhaseFault.Active
Inverter-Motor phase fault (17) - Alarm status
1
DI1069
BV1298
AuxPrb_1.Enable_W
Auxiliary probe 1 - Enable input
1
DI107
BV565
Al_Inv18_FanFault.Active
Inverter-Internal fan fault (18) - Alarm status
1
DI1070
BV1299
Al_Inv19_SpeedFault.Active
Inverter-Speed fault (19) - Alarm status
1
DI1071
BV1300
Al_Inv20_PFC_Failure.Active
Inverter-PFC module error (20) - Alarm status
1
DI1072
BV1301
Al_Inv21_PFC_OverVolt.Active
Inverter-PFC overvoltage (21) - Alarm status
1
DI1073
BV1302
Al_Inv22_PFC_UnderVolt.Active
Inverter-PFC undervoltage (22) - Alarm status
1
DI1074
BV1303
Al_Inv23_STO_Survey1.Active
Inverter-STO detection error (23) - Alarm status
1
DI1075
BV1304
Al_Inv24_STO_Survey2.Active
Inverter-STO detection error (24) - Alarm status
1
DI1076
BV1305
Al_Inv25_GroundFault.Active
Inverter-Ground fault (25) - Alarm status
1
DI1077
BV1306
Al_Inv26_ADC_ConvSync.Active
Inverter-ADC conversion sync fault (26) - Alarm status
1
DI1078
BV1307
Al_Inv27_HW_Sync.Active
Inverter-HW sync fault (27) - Alarm status
1
DI1079
BV1308
AuxPrb_1.Confi gured_R
Auxiliary probe 1 - Analog input confi gured
1
DI108
BV566
Al_Inv28_DrvOvrld.Active
Inverter-Drive overload (28) - Alarm status
1
DI1080
BV1309
Al_Inv29_uCSafe_DriveStop.Active
Inverter-Drive overtemperature (HW) (29) - Alarm status
1
DI1081
BV1310
Al_Inv99_UnexpectedStop.Active
Inverter-Unexpected stop (99) - Alarm status
1
DI1082
BV1311
Al_StartFail_BLDC1.Active
BLDC-Starting failure - Alarm status
1
DI1083
BV1312
Al_SwPrototype.Active
Prototype software - Alarm status
1
DI1084
BV1313
Al_retain.Active
High number of retain memory writings - Alarm status
1
DI1085
BV1314
Al_Err_retain_write.Active
Error in retain memory writings - Alarm status
1
DI1086
BV1315
Al_Offl
ine_THTN.Active
th - Tune offl
ine - Alarm status
1
DI1087
BV1316
Al_LowSupplyTemp.Active
Low supply temperature - Alarm status
1
DI1088
BV1317
AuxPrb_1.PrbOk_R
Auxiliary probe 1 - Probe working correctly
1
DI109
BV567
Warn_MainCoilTOutOfRange.Active
Main coil water temperature out of range warning -
Alarm status
1
DI1090
BV1318
Al_SupplyAirFlwSwWarn.Active
Supply air fl ow warning - Alarm status
1
DI1091
BV1319
Al_RetAirFlwSwWarn.Active
Return air fl ow warning - Alarm status
1
DI1092
BV1320
Al_AirFlwSwWarn.Active
Air fl ow warning - Alarm status
1
DI1093
BV1321
Warn_AFreezeWarn.Active
Antifreeze warning - Alarm status
1
DI1094
BV1322
Al_HumAlrm.Active
Humidifi er alarm - Alarm status
1
DI1095
BV1323
Al_WrkHrs_Hum.Active
Warning - Humidifi er maintenance required - Alarm status
1
DI1096
BV1324
Al_WrkHrs_SupplyFan.Active
Warning - Supply fan maintenance required - Alarm status
1
DI1097
BV1325