10.1.4 E. Heat recovery
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
HE
A
T
R
E
CO
VE
RY
E001
Heat recovery delta for bypass damper in cooling mode
4.0
-99.9
99.9
K
R/W HR1458
AV2966
Heat recovery delta for bypass damper in heating mode
4.0
-99.9
99.9
K
R/W HR1459
AV2967
E004
Heat exchanger PID parameters - Proportional gain
8.0
0.0
999.9
-
R/W HR1460
AV2968
Heat exchanger PID parameters - Integral time
120
0
999
-
R/W HR1461
PIV2969
E008
Heating exchanger type
0
0
4
-
R
HR1293
PIV2801
Bypass damper: minimum opening threshold
-5.0
-50.0
30.0
°C
R/W HR1462
AV2970
Bypass damper: maximum opening threshold
-10.0
-50.0
30.0
°C
R/W HR1463
AV2971
E012
Minimum time between heat exchanger defrost
15
0
999
min
R/W HR1464
PIV2972
Maximum defrost heat exchanger duration
15
0
999
min
R/W HR1466
PIV2973
E016
Exhaust temperature threshold for defrost
20.0
-50.0
90.0
°C
R/W HR1468
AV2974
E020
Stratifi cation correction factor of the room temperature
0.0
0.0
10.0
K
R/W HR1469
AV2975
Tab. 10.f
10.1.5
F
. Humidifi er
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
HUMI
D
I
F
IE
R
F004
Humidifi cation PID parameters - Proportional gain
8.0
0.0
999.9
-
R/W HR1549
AV3050
Humidifi cation PID parameters - Integral time
120
0
999
-
R/W HR1550
PIV3051
Humidifi cation PID parameters - Derivative time
0
0
999
-
R/W HR1551
PIV3052
F008
Humidifi er: Max humidity threshold
80.0
1.0
100.0
%rh
R/W HR1552
AV3053
Humidifi er: Max humidity proportional part
8.0
0.0
999.0
-
R/W HR1553
AV3054
Humidifi er: Max humidity integral time
50
0
999
s
R/W HR1554
PIV3055
F012
Low supply temperature threshold
16.0
0.0
25.0
°C
R
HR1354
AV2862
Humidifi er: Min temperature proportional part (Only adiabatic hum) 8.0
0.0
999.0
-
R/W HR1555
AV3056
Humidifi er: Min temperature integral time (Only adiabatic hum)
100
0
999
s
R/W HR1556
PIV3057
F020
Parameters for device confi guration - Timings for washing
operations - Delay time between two consecutive washes (mins)
30
0
999
-
R/W HR1557
IV3058
Parameters for device confi guration - Timings for washing
operations - No production time for inactivity wash (hours)
24
0
999
-
R/W HR1558
IV3059
Parameters for device confi guration - Timings for washing
operations - Washing phase time (fi ll + drain) (mins)
2
0
99
-
R/W HR1559
IV3060
F024
Manual drain request: FALSE=no request; TRUE=request to drain
-
0
1
-
R/W CS252
BV252
F028
Number of working hours left before check the humidifi er cylinder -
0
65535
-
R
IR514
PIV3828
Parameters for device confi guration - Hours counter reset request -
0
1
-
R/W CS253
BV253
Tab. 10.g
10.1.6
G
.
F
ilters
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
F
ILTE
RS
G001
Delay time for dirty fi lter by DIN
10
0
999999
s
R/W HR1560
PIV3061
HEPA fi lter alarm threshold
100.0
-9999.0
9999.0
%
R/W HR1562
AV3062
Tab. 10.h
10.1.7 H.
A
uxiliary regulation
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
A
U
X
ILI
ARY
R
E
G
UL
A
TI
ON
H001
Auxiliary Regulation 1 - Input selection
0
0
13
-
R/W HR1584
PIV3079
Auxiliary Regulation 1 - Output selection
0
0
1
-
R/W HR1585
PIV3080
H003
Auxiliary Regulation 1 - Dout: Error value
FALSE 0
1
-
R/W CS261
BV261
Auxiliary Regulation 1 - Modulating: Error value
0.0
0.0
100.0
-
R/W HR1586
AV3081
Auxiliary Regulation 1 - Enable selection
0
0
5
-
R/W HR1587
PIV3082
Auxiliary Regulation 1 - Enable selection: Manual enabling
FALSE 0
1
-
R/W CS262
BV262
Содержание k.Air
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 188: ...188 k air 030220981 rel 1 2 01 12 2020 Note...
Страница 189: ...189 k air 030220981 rel 1 2 01 12 2020 Note...
Страница 190: ...190 k air 030220981 rel 1 2 01 12 2020 Note...
Страница 191: ......