79
Functions
k.air +030220981 rel. 1.2 - 01.12.2020
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
FANS
Ba06
Air fl ow switch check type: 0=none; 1=common; 2=separated;
0
0
3
-
R/W HR1494
PIV2995
Air fl ow check type
0
0
2
-
R/W HR1495
PIV2996
Number of retry after return or supply air fl ow switch error detected
during start up procedure before turn off the unit
3
0
9
-
R/W HR1496
PIV2997
Timeout for air fl ow switch detection (seconds)
15
1
999
s
R/W HR1497
PIV2998
Air fl ow switch alarm delay time in running mode (s)
3
0
999
s
R/W HR1498
PIV2999
Ba09
Air fl ow check pressure threshold
50.0
0.0
9999.0 Pa
R/W HR1499
AV3000
Priority between minimum ventilation and night free cooling
(FALSE: minimum ventilation; TRUE: free cooling)
FALSE 0
1
-
R/W CS249
BV249
Tab. 9.am
9.18.3
F
an speed in the event of control probe alarm
In the event of a control probe alarm (diff erential pressure or air quality probe), the supply/return fans are forced on at a fi xed
speed, which can be set by parameter.
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
FANS
Bb01
Supply fan request in case of air pressure probe error
25.0
0.0
100.0
-
R/W HR1563
AV3063
Bc01
Return fan request in case of air pressure probe error
35.0
0.0
100.0
-
R/W HR1470
AV2976
Tab. 9.an
9.18.4
N
ight freecooling and ventilation
At night, based on set start and end times, the minimum ventilation and/or freecooling functions can be enabled. If the condi-
tions for enabling both functions are met, it is possible to decide which of the two will be activated, setting the priority:
1. if night freecooling is activated, the fans can be forced on at maximum speed;
2. if night ventilation is activated, the maximum fan speed limit can be set, so as to attenuate the noise level.
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
FANS
Ba18
Enable night minimum ventilation
FALSE 0
1
-
R/W CS248
BV248
Night minimum ventilation: starting hour
22
0
23
h
R/W HR1501
PIV3002
Night minimum ventilation: starting minutes
0
0
59
min
R/W HR1502
PIV3003
Night minimum ventilation: ending hour
6
0
23
h
R/W HR1503
PIV3004
Night minimum ventilation: ending minutes
0
0
59
min
R/W HR1504
PIV3005
Ba21
Night minimum ventilation request
50.0
0.0
100.0
-
R/W HR1505
AV3006
Priority between minimum ventilation and night free cooling
(FALSE: minimum ventilation; TRUE: free cooling)
FALSE 0
1
-
R/W CS249
BV249
Tab. 9.ao
9.18.5
F
ilters
k.air can manage the following fi lters:
• Supply fi lter 1 alarm
• Supply fi lter 2 alarm
• Return fi lter alarm
• Filter alarm
• HEPA fi lter 1 alarm (diff erential pressure transducer)
• HEPA fi lter 2 alarm (diff erential pressure transducer)
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
U
N
IT
Ac16
Filters confi guration
0
0
6
-
R/W HR1305
PIV2813
HEPA Filter confi guration (0: None; 1: Filt 1; Filt 1 & 2)
0
0
2
-
R/W HR1306
PIV2814
Tab. 9.ap