129
Parameter table
k.air +030220981 rel. 1.2 - 01.12.2020
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
CO
M
PR
E
SSOR
Uc44
Inverter Power Plus Info - FB version x
-
0
9
-
R
IR591
PIV3905
Inverter Power Plus Info - FB version y
-
0
9
-
R
IR592
PIV3906
Inverter Power Plus Info - FB version zzz
-
0
999
-
R
IR593
PIV3907
Inverter Power Plus Info - FB version beta
-
0
9
-
R
IR594
PIV3908
Automatically generated - Bootloader version
-
0
65535
-
R
IR595
PIV3909
Automatically generated - Firmware version
-
0
65535
-
R
IR596
PIV3910
Automatically generated - Firmware checksum
-
0
65535
-
R
IR597
PIV3911
Automatically generated - Motor control version
-
0
65535
-
R
IR598
PIV3912
Automatically generated - Hardware identifi cation
-
0
65535
-
R
IR599
PIV3913
Tab. 10.l
10.1.11 V.
EEV
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
EEV
V001
Superparameters - Valve
0
MskLimMin MskLimMax -
R/W HR1752 IV3238
Superparameters - Main regulation
19
MskLimMin MskLimMax -
R
IR566
IV3880
Superparameters - Main regulation
19
MskLimMin MskLimMax -
R
IR566
IV3880
V002
EVD parameters - Regulation parameters confi guration -
Refrigerant
0
MskLimMin MskLimMax -
R/W HR1753 IV3239
V003
Probes data - Probe S1 - Value
-
-999.9
999.9
bar
R
IR567
AV3881
Probes data - Probe S2 - Value
-
-999.9
999.9
°C
R
IR568
AV3882
Probes data - Probe S3 - Value
-
-999.9
999.9
bar
R
IR569
AV3883
Probes data - Probe S4 - Value
-
-999.9
999.9
°C
R
IR570
AV3884
V004
Superheat setpoint: cooling mode
6.0
MskLimMin MskLimMax K
R/W HR1754 AV3240
Superheat setpoint: heating mode
6.0
MskLimMin MskLimMax K
R/W HR1755 AV3241
V005
EEV start opening ratio: cooling mode
80
MskLimMin MskLimMax -
R/W HR1756 IV3242
EEV start opening ratio: heating mode
75
MskLimMin MskLimMax -
R/W HR1757 IV3243
EVD parameters - Regulation parameters confi guration -
Regulation starting delay
0
MskLimMin MskLimMax s
R/W HR1758 IV3244
V006
Enable liquid solenoid valve
-
0
1
-
R/W CS384
BV383
EVD parameters - Regulation parameters confi guration -
Standby valve opening position %
0
MskLimMin MskLimMax %
R/W HR1759 IV3245
V007
EEV Proportional gain: cooling mode
15.0
MskLimMin MskLimMax -
R/W HR1760 AV3246
EEV Integral time: cooling mode
150.0
MskLimMin MskLimMax s
R/W HR1761 AV3247
EEV Integral time: cooling mode
1.0
MskLimMin MskLimMax s
R/W HR1762 AV3248
V008
EEV Proportional gain: heating mode
15.0
MskLimMin MskLimMax -
R/W HR1763 AV3249
EEV Integral time: heating mode
150.0
MskLimMin MskLimMax s
R/W HR1764 AV3250
EEV Integral time: cooling mode
1.0
MskLimMin MskLimMax s
R/W HR1765 AV3251
V009
EVD parameters - Regulation parameters confi guration -
LowSH (low superheat) alarm timeout
0
MskLimMin MskLimMax s
R/W HR1766 IV3252
EEV Low superheat threshold: cooling mode
1.0
MskLimMin MskLimMax K
R/W HR1767 AV3253
EEV Low superheat integral time: cooling mode
10.0
MskLimMin MskLimMax s
R/W HR1768 AV3254
V010
EEV Low superheat threshold: heating mode
1.0
MskLimMin MskLimMax K
R/W HR1769 AV3255
EEV Low superheat integral time: heating mode
10.0
.MskLimMin MskLimMax s
R/W HR1770 AV3256
V011
EVD parameters - Regulation parameters confi guration -
LOP (low evaporating temperature) alarm timeout
0
MskLimMin MskLimMax s
R/W HR1771 IV3257
EEV LOP threshold: cooling mode
-5.0
MskLimMin MskLimMax °C
R/W HR1772 AV3258
EEV LOP integral time: cooling mode
5.0
MskLimMin MskLimMax s
R/W HR1773 AV3259
V012
EEV LOP threshold: heating mode
-50.0
MskLimMin MskLimMax °C
R/W HR1774 AV3260
EEV LOP integral time: heating mode
5.0
MskLimMin MskLimMax s
R/W HR1775 AV3261
V013
EVD parameters - Regulation parameters confi guration -
MOP (high evaporating temperature) alarm timeout
0
MskLimMin MskLimMax s
R/W HR1776 IV3262
EEV MOP threshold: cooling mode
30.0
MskLimMin MskLimMax °C
R/W HR1777 AV3263
EEV MOP integral time: cooling mode
15.0
MskLimMin MskLimMax s
R/W HR1778 AV3264
V014
EEV MOP threshold: heating mode
20.0
MskLimMin MskLimMax °C
R/W HR1779 AV3265
EEV MOP integral time: heating mode
15.0
MskLimMin MskLimMax s
R/W HR1780 AV3266
V015
EEV enable manual position
FALSE 0
1
-
R/W CS385
BV384
EEV manual poition steps
0
MskLimMin RegMaxPos.
Val
-
R/W HR1781 IV3267
V016
EVD parameters - System confi guration - DC power supply enabling FALSE 0
1
-
R/W CS386
BV385
V017
EVD parameters - Regulation parameters confi guration -
Low suction temperature alarm threshold
0.0
MskLimMin .MskLimMax °C
R/W HR1782 AV3268
EVD parameters - Regulation parameters confi guration -
Low suction temperature alarm timeout
0
MskLimMin MskLimMax s
R/W HR1783 IV3269
Содержание k.Air