121
Parameter table
k.air +030220981 rel. 1.2 - 01.12.2020
10.1.8 I. IE
C
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
IE
C
I001
IEC: PID parameters - Proportional gain
8.0
0.0
999.9
-
R/W HR1646
AV3141
IEC: PID parameters - Integral time
120
0
999
-
R/W HR1647
PIV3142
I005
IEC: Return humidity activation threshold
75.0
0.0
100.0
%rh
R/W HR1648
AV3143
IEC: Return humidity activation diff erential
2.0
0.0
20.0
%rh
R/W HR1649
AV3144
I010
IEC: Exhaust humidity limit threshold
95.0
0.0
100.0
%rh
R/W HR1650
AV3145
IEC: Exhaust humidity limit proportional gain
10.0
0.0
999.9
-
R/W HR1651
AV3146
IEC: Exhaust humidity limit integral time
60
0
999
s
R/W HR1652
PIV3147
I015
IEC: Fresh air damper maximum limitation
0.0
0.0
100.0
%
R/W HR1653
AV3148
Tab. 10.j
10.1.9
J
. V
D
I
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
V
D
I
Ja01
VDI Inactivity startup activation delay
48
0
65535
h
R/W HR1686
PIV3181
VDI Inactivity startup duration
5
0
65535
min
R/W HR1687
PIV3182
VDI high saturation humidity threshold
80.0
0.0
99.0
%rh
R/W HR1688
AV3183
VDI high saturation humidity diff erential
2.0
0.0
99.0
%rh
R/W HR1689
AV3184
Ja02
VDI Type: 0: Standard; 1: Custom
0
0
1
-
R/W HR1690
PIV3185
Enable of the VDI function
TRUE
0
1
-
R/W CS296
BV296
Month selection variable
4
0
5
-
R/W HR1691
PIV3186
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
TRUE
0
1
-
R/W CS297
BV297
Enable of the VDI function
TRUE
0
1
-
R/W CS298
BV298
Month selection variable
3
0
5
-
R/W HR1692
PIV3187
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
TRUE
0
1
-
R/W CS299
BV299
Ja03
Enable of the VDI function
TRUE
0
1
-
R/W CS300
BV300
Month selection variable
1
0
5
-
R/W HR1693
PIV3188
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
TRUE
0
1
-
R/W CS301
BV301
Enable of the VDI function
TRUE
0
1
-
R/W CS302
BV302
Month selection variable
3
0
5
-
R/W HR1694
PIV3189
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
TRUE
0
1
-
R/W CS303
BV303
Ja06
Enable of the VDI function
TRUE
0
1
-
R/W CS304
BV304
Month selection variable
2
0
5
-
R/W HR1695
PIV3190
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
TRUE
0
1
-
R/W CS305
BV305
Enable of the VDI function
TRUE
0
1
-
R/W CS306
BV306
Month selection variable
2
0
5
-
R/W HR1696
PIV3191
Reset timings after the inspection
-
0
1
-
R/W CS307
BV307
Ja09
Enable of the VDI function
TRUE
0
1
-
R/W CS308
BV308
Month selection variable
2
0
5
-
R/W HR1697
PIV3192
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
TRUE
0
1
-
R/W CS309
BV309
Enable of the VDI function
TRUE
0
1
-
R/W CS310
BV310
Month selection variable
2
0
5
-
R/W HR1698
PIV3193
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
TRUE
0
1
-
R/W CS311
BV311
Ja12
Enable of the VDI function
TRUE
0
1
-
R/W CS312
BV312
Month selection variable
1
0
5
-
R/W HR1699
PIV3194
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
TRUE
0
1
-
R/W CS313
BV313
Enable of the VDI function
TRUE
0
1
-
R/W CS314
BV314
Month selection variable
1
0
5
-
R/W HR1700
PIV3195
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
TRUE
0
1
-
R/W CS315
BV315
Ja15
Enable of the VDI function
TRUE
0
1
-
R/W CS316
BV316
Month selection variable
1
0
5
-
R/W HR1701
PIV3196
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
TRUE
0
1
-
R/W CS317
BV317
Enable of the VDI function
TRUE
0
1
-
R/W CS318
BV318
Month selection variable
1
0
5
-
R/W HR1702
PIV3197
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
TRUE
0
1
-
R/W CS319
BV319
Ja18
Enable of the VDI function
TRUE
0
1
-
R/W CS320
BV320
Month selection variable
2
0
5
-
R/W HR1703
PIV3198
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
TRUE
0
1
-
R/W CS321
BV321
Enable of the VDI function
TRUE
0
1
-
R/W CS322
BV322
Month selection variable
3
0
5
-
R/W HR1704
PIV3199
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
TRUE
0
1
-
R/W CS323