126
Parameter table
k.air +030220981 rel. 1.2 - 01.12.2020
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
CO
M
PR
E
SSOR
Uc06
Inverter Power Plus Info - Speed register bit 14
-
0
1
-
R
DI743
BV1201
Inverter Power Plus Info - Speed register bit 13
-
0
1
-
R
DI744
BV1202
Inverter Power Plus Info - Speed register bit 12
-
0
1
-
R
DI745
BV1203
Inverter Power Plus Info - Speed register bit 11
-
0
1
-
R
DI746
BV1204
Inverter Power Plus Info - Speed register bit 10
-
0
1
-
R
DI747
BV1205
Inverter Power Plus Info - Speed register bit 09
-
0
1
-
R
DI748
BV1206
Inverter Power Plus Info - Speed register bit 08
-
0
1
-
R
DI749
BV1207
Inverter Power Plus Info - Speed register bit 07
-
0
1
-
R
DI750
BV1208
Inverter Power Plus Info - Speed register bit 06
-
0
1
-
R
DI751
BV1209
Inverter Power Plus Info - Speed register bit 05
-
0
1
-
R
DI752
BV1210
Inverter Power Plus Info - Speed register bit 04
-
0
1
-
R
DI753
BV1211
Inverter Power Plus Info - Speed register bit 03
-
0
1
-
R
DI754
BV1212
Inverter Power Plus Info - Speed register bit 02
-
0
1
-
R
DI755
BV1213
Inverter Power Plus Info - Speed register bit 01
-
0
1
-
R
DI756
BV1214
Inverter Power Plus Info - Speed register bit 00
-
0
1
-
R
DI757
BV1215
Uc07
Automatically generated - Motor Overload Accumulator
-
-999.9
999.9
-
R
IR584
AV3898
Automatically generated - Drive Overload Accumulator
-
-999.9
999.9
-
R
IR585
AV3899
Uc08
Compressor model (PowerPlus)
1
0
120
-
R/W HR1790
PIV3276
Compressor model
1
1
120
-
R/W HR1791
PIV3277
Drive type
0
0
12
-
R/W HR1792
PIV3278
Drive type
0
0
12
-
R
HR1792
PIV3278
Write default request
0
0
1
-
R/W HR1793
IV3279
Inverter Power Plus Info - Reserved
-
0
1
-
R
DI758
BV1216
Inverter Power Plus Info - Reserved
-
0
1
-
R
DI759
BV1217
Uc09
Inverter Power Plus Info - Main supply as three phases
-
0
1
-
R
DI760
BV1218
Inverter Power Plus Info - Device rated current [AA.a]
-
-99.0
99.0
-
R
IR586
AV3900
Inverter Power Plus Info - Three-phase inverter required for compres-
sor
-
0
1
-
R
DI761
BV1219
Inverter Power Plus Info - Rated current of compressor
-
0
99
-
R
IR587
PIV3901
Uc10
Curr compressor confi guration (Powerplus) - Data communication
fault timeout
-
0
600
-
R/W HR1794
PIV3280
Serial number control enable
FALSE
0
1
-
R/W CS389
BV388
Uc11
Curr compressor confi guration (Powerplus) - Min output frequency
-
UI_FreqLi-
mitMin
UI_ FreqLi-
mit500Hz
-
R/W HR1795
AV3281
Curr compressor confi guration (Powerplus) - Max output frequency
-
UI_FreqLi-
mitMin
UI_ FreqLi-
mit500Hz
-
R/W HR1796
AV3282
Uc12
Curr compressor confi guration (Powerplus) - Skip frequency: set 1
-
UI_FreqLi-
mitMin
UI_ FreqLi-
mit500Hz
-
R/W HR1797
AV3283
Curr compressor confi guration (Powerplus) - Skip frequency: band 1
-
UI_FreqLi-
mitMin
UI_ FreqLi-
mit500Hz
-
R/W HR1798
AV3284
Uc13
Curr compressor confi guration (Powerplus) - Skip frequency setpoint
2
-
UI_FreqLi-
mitMin
UI_ FreqLi-
mit500Hz
-
R/W HR1799
AV3285
Curr compressor confi guration (Powerplus) - Skip frequency band 2
-
UI_FreqLi-
mitMin
UI_ FreqLi-
mit500Hz
-
R/W HR1800
AV3286
Uc14
Curr compressor confi guration (Powerplus) - Skip frequency setpoint
3
-
UI_FreqLi-
mitMin
UI_ FreqLi-
mit500Hz
-
R/W HR1801
AV3287
Curr compressor confi guration (Powerplus) - Skip frequency band 3
-
UI_FreqLi-
mitMin
UI_ FreqLi-
mit500Hz
-
R/W HR1802
AV3288
Uc15
Curr compressor confi guration (Powerplus) - Switching frequency
-
0
2
-
R/W HR1803
PIV3289
Curr compressor confi guration (Powerplus) - Switching frequency
derating
-
0
1
-
R/W HR1804
PIV3290
Uc16
Curr compressor confi guration (Powerplus) - Motor overtemperature
alarm (PTC) enable
-
0
1
-
R/W HR1805
PIV3291
Curr compressor confi guration (Powerplus) - Motor overtemperature
alarm delay
-
0
999
-
R/W HR1806
PIV3292
Uc17
Curr compressor confi guration (Powerplus) - Reverse speed enable
-
0
1
-
R/W HR1807
PIV3293
Curr compressor confi guration (Powerplus) - Speed derating mode
-
0
10
-
R/W HR1808
PIV3294
Uc18
Curr compressor confi guration (Powerplus) - Stop mode
-
0
1
-
R/W HR1809
PIV3295
Curr compressor confi guration (Powerplus) - Flying restart
-
0
1
-
R/W HR1810
PIV3296
Uc19
Curr compressor confi guration (Powerplus) - Relay confi guration
-
0
8
-
R/W HR1811
PIV3297
Uc20
Motor pole pairs
0
0
9
-
R
HR1812
PIV3298
Motor pole pairs
0
0
9
-
R/W HR1812
PIV3298
Curr compressor confi guration (Powerplus) - Motor control mode
-
0
2
-
R/W HR1813
PIV3299
Uc21
Curr compressor confi guration (Powerplus) - Motor base frequency
-
UI_FreqLi-
mitMin
UI_ FreqLi-
mit500Hz
-
R/W HR1814
AV3300
Curr compressor confi guration (Powerplus) - Motor base voltage
-
UI_MotBa-
seV_
MinLim
.UI_MotBa-
seV_
MaxLim
-
R/W HR1815
PIV3301
Содержание k.Air
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 188: ...188 k air 030220981 rel 1 2 01 12 2020 Note...
Страница 189: ...189 k air 030220981 rel 1 2 01 12 2020 Note...
Страница 190: ...190 k air 030220981 rel 1 2 01 12 2020 Note...