Section 7. Installation
235
Many variations of this 200-Hz measurement program are possible to achieve
other burst rates and duty cycles.
The
SubScan()
/
NextSubScan
instruction pair introduce added complexities.
The
SubScan() / NextSubScan Details
,
introduces some of these. Caution dictates
that a specific configuration be thoroughly tested before deployment. Generally,
faster rates require measurement of fewer channels. When testing a program,
monitoring the
SkippedScan
,
BuffDepth
, and
MaxBuffDepth
registers in the CR800
Status
table may give insight into the use of buffer resources. Bear in mind that
when the number of
Scan()
/
NextScan
buffers is exceeded, a skipped scan, and
so a missed-data event, will occur.
7.8.12.2.1 SubScan() / NextSubScan Details
•
The number of
Counts
(loops) of a sub-scan is limited to 65535
•
Sub-scans exist only within the
Scan()
/
NextScan
structure with the
Scan()
interval set large enough to allow a sub-scan to run to completion of its
counts.
•
Sub-scan interval (i) multiplied by the number of sub-scans (n) equals a
measure time fraction (MT
1
), a part of "measure time", which measure time is
represented in the
MeasureTime
register in table
Status Table Fields and
Descriptions
(p. 506).
The
EndScan
instruction occupies an additional 100 µs
of measure time, so the interval of the main scan has to be
≥
100 µs plus
measure time outside the
SubScan()
/
EndSubScan
construct, plus the time
sub-scans consume.
•
Because the task sequencer controls sub-scans, it is not finished until all sub-
scans and any following tasks are complete. Therefore, processing does not
start until sub-scans are complete and the task sequencer has set the delay for
the start of the next main scan. So, one
Scan()
/
NextScan
buffer
holds all
the raw measurements inside (and outside) the sub-scan; that is, all the
measurements made in a single main scan. For example, one execution of the
following code sequence stores 30000 measurements in one buffer:
Scan
(40,Sec,3,0)
'Scan(interval, units, buffers, count)
SubScan
(2,mSec,10000)
VoltSe
(Measurement(),3,mV5000,1,False,150,250,1.0,0)
CallTable
All4
NextSubScan
NextScan
Note
measure time in the previous code is 300 µs + 19 ms, so a
Scan()
interval
less than 20 ms will flag a compile error.
•
Sub scans have the advantage of going at a rate faster than 100 Hz. But
measurements that can run at an integral 100 Hz have an advantage as
follows: since all sub-scans have to complete before the task sequencer can
set the delay for the main scan, processing is delayed until this point (20 ms
in the above example). So more memory is required for the raw buffer space
for the sub-scan mode to run at the same speed as the non-sub-scan mode,
and there will be more delay before all the processing is complete for the
burst. The pipeline (the raw buffer) has to fill further before processing can
start.
Содержание CR850
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 26: ...Table of Contents 26...
Страница 30: ...Section 2 Cautionary Statements 30...
Страница 32: ...Section 3 Initial Inspection 32...
Страница 35: ...Section 4 Quickstart Tutorial 35 Figure 2 Wiring panel...
Страница 55: ...Section 4 Quickstart Tutorial 55 Figure 24 PC200W View data utility...
Страница 78: ...Section 5 System Overview 78...
Страница 80: ...Section 6 CR800 Specifications 80...
Страница 95: ...Section 7 Installation 95 Figure 35 DevConfig OS download window Figure 36 Dialog box confirming OS download...
Страница 104: ...Section 7 Installation 104 Figure 43 Include File settings via DevConfig Figure 44 Include File settings via PakBusGraph...
Страница 267: ...Section 7 Installation 267 Figure 84 Running average signal attenuation...
Страница 268: ...Section 7 Installation 268...
Страница 384: ...Section 8 Operation 384 Figure 113 Using the keyboard display...
Страница 385: ...Section 8 Operation 385 8 8 1 Data Display Figure 114 Displaying data with the keyboard display...
Страница 387: ...Section 8 Operation 387 Figure 116 Real time custom...
Страница 388: ...Section 8 Operation 388 8 8 1 3 Final Storage Tables Figure 117 Final storage tables...
Страница 389: ...Section 8 Operation 389 8 8 2 Run Stop Program Figure 118 Run Stop Program...
Страница 390: ...Section 8 Operation 390 8 8 3 File Display Figure 119 File display...
Страница 396: ...Section 8 Operation 396...
Страница 402: ...Section 9 Maintenance 402...
Страница 450: ...Section 11 Glossary 450...
Страница 504: ...Appendix A CRBasic Programming Instructions 504...
Страница 526: ...Appendix B Status Table and Settings 526...
Страница 530: ...Appendix C Serial Port Pinouts 530...
Страница 536: ...Appendix E FP2 Data Format 536...
Страница 550: ...Appendix F Other Campbell Scientific Products 550...
Страница 564: ...Index 564 WriteIO 464 Writing Program 108 X XML 448 XOR 473 Y Y intercept 141 142 Z Zero 155 166 Zero Basis 151...
Страница 565: ......